PACSystems™ RX3i PROFINET Controller
IC695PNC001-BDBD
Firmware Version 3.16
1
Includes conformal coat and low temperature module variants, if available.
2
The last two characters of the catalog number suffix may not increment with every firmware release beginning with IC695PNC001-BCBD Release 3.15.
1 2
IMPORTANT PRODUCT INFORMATION
GFK-2573Z
Sep 2020

Advertisement

Table of Contents
loading

Summary of Contents for Emerson PACSystems RX3i PROFINET

  • Page 1 IMPORTANT PRODUCT INFORMATION GFK-2573Z Sep 2020 PACSystems™ RX3i PROFINET Controller IC695PNC001-BDBD Firmware Version 3.16 Includes conformal coat and low temperature module variants, if available. The last two characters of the catalog number suffix may not increment with every firmware release beginning with IC695PNC001-BCBD Release 3.15.
  • Page 2 Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that Emerson may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the Emerson products referenced herein.
  • Page 3: Ordering Information

    Ethernet traffic such as ping and telnet. Features of the RX3i PNC001 include: ▪ Full configuration services for the RX3i PROFINET Controller, plus all connected Emerson and third-party I/O- Devices using PAC Machine Edition (PME). ▪...
  • Page 4 Maximum surrounding air temperature without a fan. A lower maximum temperature may be required depending on PNC001 location and SFP population. Refer to the section, Operating Range for Surrounding Air Temperature (section 1.4) in PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571K or later. Number of Port Connectors...
  • Page 5: Emc Installation Requirements

    GFK-2573Z Sep 2020 EMC Installation Requirements To meet EN 55011 and FCC Class A radiated emissions, the Control system in which the IC695PNC001 module is used shall be mounted in a metal enclosure when three or more IC695PNC001 modules are used. All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity.
  • Page 6: Status Reporting

    GFK-2573Z Sep 2020 ATEX Zone 2 This module must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2, Group IIC and rated IP54. The enclosure shall only be able to be opened with the use of a tool. Status Reporting The PNC001 provides 32 bits of status information to a configured location in the RX3i CPU’s reference memory.
  • Page 7 LEDs on the PROFINET Controller Module The table below summarizes LED functions. Note that there are differences between the -Ax version and the -Bxxx version. For detailed information refer to Installation and Diagnostics in PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571K or later.
  • Page 8: Quick Start

    GFK-2573Z Sep 2020 Quick Start Before installing and operating the PNC001, refer to PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571 for detailed information. Installation and initial startup procedures for the PNC001 include the following steps: 1. Pre-Installation check 2. Installing the PNC001 in an RX3i backplane The PNC001 must be installed in the main (CPU) rack of the RX3i system, using a Universal Backplane such as IC695CHS007, CHS012 or CHS016.
  • Page 9: Release History

    PME is the primary tool used to configure an RX3i PROFINET network. In addition, certain parameters can be set from a computer through the PNC001’s Command Line Interface. For details on system planning and configuration, refer to PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571, Chapter 3. CAUTION Whenever an RX3i PNC001 is extracted from a powered RX3i backplane, it loses power immediately which may result in data loss.
  • Page 10 GFK-2573Z Sep 2020 Version Firmware Date Comments Revision Supports the Remote Get HART Device Information COMMREQ. Information from a HART device connected to an RX3i Analog Module in an IC695PNS001 RX3i IC695PNC001-AM 2.26 PROFINET Scanner may be read into the user application using the Remote Get HART 2016 Device Information COMMREQ.
  • Page 11: New Features And Enhancements

    GFK-2573Z Sep 2020 Upgrades Upgrade Kit: 41G2472-FW01-000-A4 Only IC695PNC001-Bxxx or later revision modules are field upgradable to this release using the upgrade kit listed above. IC695PNC001-Ax modules cannot be upgraded with this kit due to hardware and firmware design changes in the PNC001-Bxxx revision.
  • Page 12 GFK-2573Z Sep 2020 Functional Compatibility The following CPU firmware and programming software versions are required to use the features introduced in PNC001 release 2.00 and later: Subject Feature Minimum Version Required RX3i backplane RX3i backplane hardware The following minimum backplane hardware revision must be hardware used: IC695CHS012-BAMP...
  • Page 13 GFK-2573Z Sep 2020 Subject Feature Minimum Version Required RX3i PNC001 release 2.11 (or CRU320 Release 8.40 later) CPE330 Release 8.70 Hot Standby Redundancy (Other CPU models are not supported) with PROFINET I/O RX3i PNC001 Release 2.00 CRU320 Release 8.00 CPE330 Release 8.70 Hot Standby Redundancy (Other CPU models are not supported) with PROFINET I/O...
  • Page 14 GFK-2573Z Sep 2020 Subject Feature Minimum Version Required RX3i PNC001 Release 2.11(or PME 8.50 SIM 9 or 8.60 SIM 1 later) • 128 PROFINET Device Support • Critical Network Port RX3i PNC001 Release 2.00 (or PAC Machine Edition 8.00 SIM 5 later) Hot Standby Redundancy with PROFINET I/O...
  • Page 15 GFK-2573Z Sep 2020 Restrictions and Open Issues Restrictions and Open Issues related to PNC001 Operational Behavior Issue Description There are two scenarios that can cause the PNC001 to indicate that an MRP Ring is PNC001 indicates premature MRP closed when, in fact, it is still open. The scenarios are: Ring closure and logs extra Ring Closed/Ring Open faults when 1.
  • Page 16 GFK-2573Z Sep 2020 Issue Description Unexpected Loss of Device faults Loss of Device faults for currently connected devices may appear in the PLC I/O Fault table and/or PNC001 local log when the PNC001 is reset via its reset pushbutton. Unintended operation of The power flow output of the PNIO_DEV_COMM function block provides validation of PNIO_DEV_COMM function block the input parameters and confirms that the PNC001 has locally processed the...
  • Page 17 GFK-2573Z Sep 2020 Restrictions and Open Issues related to the Command Line Interface (-Ax Version Only) Restriction/Open Issues Description Invalid help response for invalid Occasionally, the CLI will return invalid help suggestions if the user attempts to get help CLI commands on an invalid command by using the question mark key.
  • Page 18: Operational Notes

    GFK-2573Z Sep 2020 Operational Notes Operational Note Description Storing updated media When storing Media Redundancy Protocol (MRP) configuration updates to an operating redundancy protocol (MRP) MRP ring network, users may infrequently observe one or more pairs of Loss of Device and configurations to large operating subsequent Addition of Device faults regarding PROFINET I/O Device faults on the network.
  • Page 19 GFK-2573Z Sep 2020 Operational Note Description Beginning with PME 8.60, the PROFINET DCP tool requires elevation to administrator PROFINET DCP – Direct privilege to run when it is launched by right-clicking on a PNC001. Since the PME Connection indicates that no valid installation does not setup PME or any of its internal tools to run at the administrator Ethernet adapters are available for privilege level, you will have to inform Windows that you want it to run PME as an...
  • Page 20: Additional Information

    For additional information, please refer to the manuals listed below. Manuals can be downloaded from the Support website. Please see the link located at the end of this document. PACSystems RX3i PROFINET I/O Controller Manual GFK-2571 PACSystems RX3i PROFINET Controller Command Line Interface Manual GFK-2572 PACSystems RX3i PROFINET Scanner Manual GFK-2737...
  • Page 21: General Contact Information

    Note: If the product is purchased through an Authorized Channel Partner, please contact the seller directly for any support. Emerson reserves the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product.