Problems During Power-Up And Reset; Transitioning To Firmware Update Mode; Special Led Blink Patterns - Emerson PACSystems RX3i User Manual

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
5.1.2

Problems During Power-up and Reset

Certain conditions can prevent the module from powering up and becoming operational or
entering firmware update mode:
Problem
Hardware failure
Invalid bootstrap image
Invalid boot image
Power-up
diagnostics/hardware
initializations fail that are
considered fatal
Non-Fatal
diagnostic/hardware
initialization faults
The module does not
contain hardware identity
information
5.1.3

Transitioning to Firmware Update Mode

The module transitions to firmware update mode for any of the following reasons:
1. WinLoader has commanded the module to enter firmware update mode. This is
2. The PNC001 does not have a valid firmware image at power-up. The PNC001
For more information about firmware update mode and using WinLoader, please see
Section 2:, Installation.
5.2

Special LED Blink Patterns

In addition to the LED blink patterns that indicate a fatal error, the PNC001's LEDs can
indicate module location/identification and microprocessor overtemperature conditions,
as described below.
Special LED Blink Patterns are not supported by RSTi-EP CPE100/CPE115 embedded
PROFINET Controller.
Diagnostics
Indication
All LEDs off. Module unresponsive.
No LEDs turn on and the module is
unresponsive, or
The STATUS LED is solid green and
is the only LED that is on.
LED Fatal Error blink code, as
described in this chapter.
The module continues normal
power-up, but an entry is added to
the Local Log table and the RX3i
CPU's Fault Table (if backplane
communications
established).
LED Fatal Error blink pattern, as
described in this chapter.
normal when a firmware update has been initiated from WinLoader.
performs checks to determine the firmware image is valid and has not been
corrupted before it begins execution. If the validation fails, firmware update mode
is activated until a valid image has been stored.
Action
Return the module Emerson.
Note the blink code and
contact Customer Service.
Note the fault and contact
Customer Service.
have
been
Note the blink code and
contact Customer Service.
Section 5
May 2021
100