Embedded Profinet Controller; Pnc001 Module Specifications - Emerson PACSystems RX3i User Manual

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
1.2.2

Embedded PROFINET Controller

CPL410, CPE400, CPE330 and CPE100/CPE115 feature an Embedded PROFINET IO-
Controller function. This feature permits LAN2 to be configured as a PROFINET Controller
like PNC001 in functionality, but without requiring the presence of a PNC001 rack-mounted
module.
In the following Specifications section, the physical specifications related to rack mounting
do not apply to the embedded PROFINET Controllers. Refer to the corresponding product
documentation for CPL410, CPE400, CPE330 and CPE100/CPE115 in the PACSystems RX7i,
RX3i and RSTi-EP CPU Reference Manual, (GFK-2222AE or later).
1.3

PNC001 Module Specifications

Specification
PROFINET Support
CPU Compatibility
Power Requirements
with no SFP devices installed
with two SFP devices
installed, 0.35A per SFP
Operating Temperature
Range
1
For CPE400, CPE330 and CPE100, CPE115 refer to the equivalent product specifications in the PACSystems RX7i, RX3i and RSTi-EP CPU
Reference Manual, (GFK-2222Z or later).
Introduction
Description
PROFINET
Redundantly controlled operation conforms to PROFINET V2.3 Type
S-2 System Redundancy.
Note that the CPE100/CPE115 is a simplex PROFINET IO-Controller.
Requires CPU315, CPU320, CPE305, CPE310 or CPE330 with
firmware version 7.0 or higher. Also compatible with all versions of
CPE302.
Simplex or redundantly-controlled PROFINET I/O requires CRU320
release 8.00 or higher.
For the current status of CPE330 features refer to PACSystems RX7i,
RX3i and RSTi-EP CPU Reference Manual, (GFK-2222Z or later).
Note that CPL410, CPE400 and CPE100/CPE115 features an
embedded PROFINET IO-Controller; these are standalone CPUs and
do not support IC695PNC001.
1
,
Rev. –Ax:
3.3Vdc: 0.5A
3.3Vdc: 1.2A maximum
5 Vdc: 1.5A maximum
Rev. -Axxx:
1
0°C to 60°C
Version
2.2
Note:
See Section 1.4 for de-rating conditions
General
Class
A
IO-Controller
Rev. –Bxxx:
3.3Vdc: 0.5A
3.3Vdc: 1.2A maximum
5 Vdc: 0.75A maximum
Rev. -Bxxx:
-25°C to 60°C