I/O Fault Contacts - Emerson PACSystems RX3i User Manual

Profinet i/o-controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
Bit
9
10
11
12
13
14-32
5.4

I/O Fault Contacts

The PROFINET Controller sets I/O point fault contacts to the faulted state whenever an IO-
Device is not available or there is a problem with the I/O module.
If the control application needs to know whether a set of inputs is available or not, it must
refer to the input point faults. For example, immediately following a power cycle or recent
download of hardware configuration, the PACSystems CPU can go to Run mode before the
PROFINET Controller and its configured IO Devices are ready to transfer inputs. During this
time, the inputs for each IO-Device are defaulted and the corresponding input point faults
remain in the faulted state until both the PROFINET Controller and the IO-Device are ready
to transfer inputs. By inspecting the input point faults, the application can determine when
the inputs are ready to be consumed.
9
Individual device statuses (as reported by the PNIO_DEV_COMM function block) are updated prior to the All Devices Connected bit.
Therefore, it is possible (depending on PNC loading) to see via the PNIO_DEV_COMM function block that every individual device is
connected while the All Devices Connected bit is not yet set. To avoid this inconsistency, it is recommended that the All Devices Connected
bit be checked first, before checking individual device connection status using the PNIO_DEV_COMM function block. For details, refer to
the section entitled
Block
PNIO_DEV_COMM Function
Diagnostics
Name
Description
All Devices
1
9
communicating over PROFINET.
Connected
0 indicates no devices are configured or one or more configured
devices have not established a PROFINET connection.
Reserved
Always 0.
MRP Enabled
0 indicates that MRP is not enabled.
1 indicates that MRP is enabled.
MRP Role
If MRP is enabled:
0 indicates that the PROFINET Controller is currently an MRP
client (MRC).
1 indicates that the PROFINET Controller is currently the MRP
Manager (MRM).
If MRP is not enabled, this bit will be set to 0.
MRP Ring
If MRP is enabled and the PROFINET Controller is currently the
Status
MRM:
0 indicates that the ring is open (ring broken).
1 indicates that the ring is closed (ring complete).
If MRP is not enabled, or if the PROFINET Controller is an MRC, this
bit will be set to 0.
Reserved
Set to 0
.
indicates
all
configured
Section 5
devices
are
connected
May 2021
and
103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rsti-ep

Table of Contents