Section 6:
The PACSystems PROFINET Controller supports PROFINET Media Redundancy Protocol
(MRP). The PROFINET Controller can be used as either a Media Redundancy Manager or
Media Redundancy Client on a redundant media ring.
Media Redundancy enables the network to recover from a failure at any single network link
or network node. Because it operates transparently to applications using the network, no
changes to the application are needed to use media redundancy.
This Section describes:
PROFINET Media Redundancy Protocol
MRP Performance
Ring Topology with One Controller
Ring Topology with Multiple Controllers
Setting Up Media Redundancy Protocol for a PROFINET IO-Controller
Sequence for Enabling Media Redundancy
Sequence for Replacing a Media Redundancy Manager
Procedure for Disabling Media Redundancy
The following table shows which PROFINET Scanners/Devices support MRP.
PROFINET Scanner/Device
RX3i CEP Carrier
RX3i Genius
PAC8000 PROFINET Scanner (PNS) Module
RSTi PROFINET Network Adaptor
RSTi-EP PROFINET Network Adaptor
RX3i PROFINET Scanner (PNS) Module
VersaMax PROFINET Scanner (PNS) Module
VersaMax IP PROFINET Scanner Module
VersaPoint PROFINET Scanner
16
Bumpless operation is only guaranteed at IO Update rates at or above 128 ms

Redundant Media

Redundant Media
TM
Communications Gateway
Acronym
PROFINET Media
Redundancy Protocol
(MRP)
RX3i CEP
RX3i GCG
PAC8000 PNS
RSTi PNS
RSTi-EP PNS
RX3i PNS
Versamax PNS
VersaMax/IP PNS
16
VersaPoint PNS
Section 6
May 2021
131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rsti-ep

Table of Contents