RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
2.8
PNC001 LED Behavior
2.8.1
Power-up LED Patterns
At power-up, the LEDs show the blink patterns described below. The LEDs also blink
diagnostic patterns for certain operating errors and for module identification. See Section
5:, Diagnostics for a description of those special blink patterns.
Step
1
1.1
1.2
2
3
4
Installation
Description
LED/Blink
pattern
All LEDs OFF
Normal operation
ACTIVE LED
Normal operation
solid green
(PNC001-Bxxx
only)
CONFIG LED
Normal operation
solid green
(PNC001-Bxxx
only)
STATUS LED
Normal operation
solid green
OK LED blinks
Fatal Initialization or
Amber with
Diagnostics Failure, Hardware
special blink
Module Identity Information
code
not available
OK, LAN, and
Invalid firmware detected.
STATUS LEDs
Module is waiting for firmware
blink green in
update. Blink pattern continues
unison (1 Hz)
during firmware update.
LAN and
Normal operation
STATUS LED
solid green
(PNC001-Ax
only)
LAN LED solid
Normal operation
green
LAN and
Update of module firmware.
STATUS LED
After the automatic update
blink green
completes, the LEDs blink
(1 Hz)
Amber and the module resets,
which restarts the power-up
process.
Figure 31: PNC001-Bxxx Front
View showing LEDs
Section 2
May 2021
41