3.8.1

Editing Third-Party IO-Device Parameters

To configure the parameters of a third-party IO-Device, either double-click on the module
in the Navigator, or right-click on the module and select Configure from the menu. Upon
opening the IO Devices configuration, you will see an IO-Device Access Point tab, a GSDML
Details tab, and, possibly, additional parameter tabs (if defined by the device manufacturer
in the associated GSDML file).
IO-Device Parameters (IO-Device Access Point Tab)
Use the IO-Device Access Point tab to set up the device's interface to the RX3i controller:
Figure 74: Third-Party I/O: Use of IO-Device Access Point Tab
Inputs Default: Choose whether the RX3i CPU will set inputs from the remote node to Off,
or Hold Last State in the following cases:
The PROFINET Controller is not operational or is removed.
The PROFINET Controller cannot communicate with the device due to cable or network
configuration issues.
The device is not able to scan the sub-module in its remote node.
I/O Scan Set: The scan set for an IO-Device defaults to scan set 1. Scan sets are defined in the
associated PLC CPU's Scan Sets tab. The valid range is 1 through 32; the default value is 1.
IO-Device Parameters (Media Redundancy Tab)
If the IO-Device supports Media Redundancy (see Section 6:, Redundant Media, for more
information), a Media Redundancy tab will be present. Open the Media Redundancy tab and
select either Client or Manager:
Figure 75: Third-Party I/O: Use of Media Redundancy Tab
If the IO-Device will be a Media Redundancy Client, click on Ring Port 1 and Ring Port 2 to
choose the module ports that will be used.
Configuration
Section 3
May 2021
77