6.2.2. ETL models with an atmospheric burner. Natural gas heating

Gas output pressure control (Fig. 6.2)
Before starting the ironing program, remove the cover
from the gas valve protection base-frame.
Insert the pressure pipe through one of the holes drilled in
the base of the base-frame.
Loosen the pressure outlet screw B (without removing it
completely). At this point, connect the pressure gauge
pressure outlet pipe.
The arrow C indicates the direction of the gas flow.
Refit the base-plate cover and start up the machine as
indicated in Section 6.1.
Approximately one minute after connecting the gas flow
solenoid
valve,
check
corresponds to the value indicated in the table in Section
4.4. The gas pressure must remain stable regardless of
possible differences in consumption caused by the
operation of other gas appliances connected to the same
line.
If this is not the case, change the adjustment of the screw
D until the pressure indicated in the table in Section 4.4 is
obtained.
Once the gas pressure control is completed:
 Stop the ironer and turn off the power and gas supply.
 Open the cover, remove the pressure gauge pipe and
tighten the screw B.
 Refit and properly secure the base-frame cover.
WARNING!
BE SURE TO TIGHTEN THE PRESSURE OUTLET SCREW (B/Fig. 6.2).
FAILURE TO DO SO WOULD RESULT IN A GAS LEAK THAT COULD CAUSE A SERIOUS ACCIDENT.
Initial start-up
that
the
output
pressure
74
Fig. 6.2
Code no. 550038
Rev. no. 16/1018