Procedure For Checking Fan Motors In Indoor Units - Hitachi RCI Service Manual

Indoor units system free series & complementary systems
Table of Contents

Advertisement

8 Troubleshooting

8.3 Procedure for checking fan motors in indoor units

Name and abbreviation of the cable colours used:
Black
Brown
BLK
BRN
Power
Indoor units
RCI-1.0FSN2E
RCI-1.5FSN2E
RCI-2.0FSN2E
RCI-3.0FSN2E
RCI-4.0FSN2E
RCI-5.0FSN2E
108 W
RCI-6.0FSN2E
RCIM-1.0FSN2
RCIM-1.5FSN2
RCIM-2.0FSN2
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.0FSN2
RCD-2.5FSN2
RCD-3.0FSN2
RCD-4.0FSN2
35 W x 2
RCD-5.0FSN2
55 W x 2
RPC-2.0FSN2E
RPC-2.5FSN2E
RPC-3.0FSN2E
234
SMGB0063 rev. 1 - 10/2010
Red
Yellow
RED
YEL
Wiring diagram
input
56 W
DC motor
DC motor
52 W
DC motor
35 W
55 W
65 W
Green
Blue
GRN
BLU
Cable no.
BLK1-3RED
RED3-5WHT
BLK1-3RED
RED3-5WHT
BLK1-3RED
RED3-5WHT
BLK1-3RED
RED3-5WHT
BLK1-2RED
RED2-3YEL
YEL3-4GRY
GRY4-5BLU
RED2-6WHT
Grey
Orange
White
GRY
ORN
WHT
Resistance (Ω)
159.00
92.00
to 20 °C
70.90
81.70
to 20 °C
159.00
92.00
to 20 °C
70.90
81.70
to 20 °C
59.90
16.90
15.80
15.80
63.60
to 20 °C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

RcimRcdRpcRpiRpimRpk ... Show all

Table of Contents