10 Servicing
10.2.10 Removal of the float switch
Remove the drain pan as indicated in chapter
pan, see on page 281.
Remove the screw securing switch securing plate to the drain pan
and remove it.
N O T E
The float switch is located at the rear of the drain pan.
Loosen the resin nut securing the float switch and remove it.
Remove the two screws securing the drain mechanism to remove
the mechanism.
N O T E
•
When refitting, make sure the hook is fitted into the groove
in the drain pan and screw into place.
•
The torque value of the resin nut is 0.3 - 0.4 Nm. If the torque value is higher, the nut will be damaged.
10.2.11 Removal of the thermistors from the liquid and gas pipes
Remove the optional air panel in line with the instructions given in
chapter
Removal of the optional air
Remove the fan duct in line with the instructions given in chapter
Removal of the fan duct and the
Remove the drain pan as indicated in chapter
pan, see on page 281.
Remove the evaporator partition plate securing the heat exchanger
by removing the five screws.
283
SMGB0063 rev. 1 - 10/2010
Removal of the drain
panel, see on page 278.
fan, see on page 280.
Removal of the drain
10