FOR SERVICE PERSONNEL ONLY
HITACHI CEILING CASSETTE-UNIT AIR
CONDITIONER INSTALLATION MANUAL
O
Read the safety precautions carefully before operating the unit.
O
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
!
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as
described in the user's guide.
!
O
Please request your sales agent or qualiÀ ed technician ti install your unit. Water leakage, sort circuit or À re may occur if you do the
installtion work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause
O
water leakage, electric shock and À re.
O
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units
may collapse and impose danger.
O
Observe the rules and regulations of the electrical installtion and the methods described in the installation manual when dealing
with the electrical work. Use power cables approved by the authorities of your country.
O
Be sure to use speciÀ ed wire for the connection indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and À re.
Please use the speciÀ ed components for installtion work. Otherwise, the units may collapse or water leakege, electric shock and
O
À re may occur.
O
Be sure to use the speciÀ ed piping set for R-22. Otherwise, this may result in broken copper pipes or faults.
O
When installing or removing an air conditioner, only speciÀ ed refrigerant (R-22) shall be allowed, do not allow air or moisture to
remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture may
be caused.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with À re, a poisonous gas
O
may occur.
O
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into
the room, coming into contact with À re in the fan-driven heater, space heater, etc., a poisonuos gas may occur.
O
Unauthorized modiÀ cations to the air conditioner may be dangerous. If a breakdown occurs please call a qualiÀ ed air conditoner
technician or electrician. Improper repairs may result in water leakage, electric shock and À re, etc.
!
O
A circuit breaker or fuse (20A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
A main switch with a contact gap of more than 3.5mm has to be installed in the power supply line to the outdoor unit.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
O
O
Do not install the unit near a location where there is Á ammable gas. The outdoor unit may catch À re if
Á ammable gas leaks around it.
For installation of front panel RAI-ZCPM, please follow exactly the instruction in the manual.
O
O
Please ensure smooth Á ow of water when installing the drain hose.
Opening of False Ceiling and Suspension Bolts
(1) Determine the À nal location and installation direction of the indoor unit
paying careful attention to the space for the piping, wiring and maintenance.
(2) Cut out the area for the indoor unit in the false ceiling and install suspension
bolts, as shown in Fig. 1.
Dimension of Opening
860 to 910
(Dimension of
Suspension Bolts)
Piping Connection
Drain Piping
Side
Connection Side
Fig. 1 Opening of False Ceiling and Suspension Bolts
(3) Check to ensure that the ceiling is horizontally level, otherwise drainage
can not Á ow.
(4) Strengthen the opening parts of the false ceiling.
(5) Mount suspension bolts, as shown in Fig. 2
* For Concrete Slab
150 to 160mm
Anchor Bolt
(W3/8 or M10)
* For Steel Beam
I Beam
Suspension Bolt
(W3/8 or M10)
Fig. 2 Mounting the Suspension Bolts
Mounting Position of the Indoor Unit
4-Suspension Bolts
M10 or W3/8 (Field-Supplied)
Surface of
Ceiling
* indicates the dimension between lower face of
indoor unit and surface of ceiling.
Fig. 3 Mounting Position
<
>
IA669: A
O
Carefully read through the procedures of proper installation
before starting installation work.
O
The sales agent should inform customers regarding the correct
operation of installation.
Tools Needed For Installation Work
O
+ –
Screwdriver
O
Measuring Tape
O
ø 65mm Power Drill
O
Hexagonal Wrench Key (
Wrench (14,17,19,22,26,27mm)
Gas Leakage Detector
O
O
Pipe Cutter
Vinyl Tape
Pliers
O
O
O
O
WARNING
4-Positions of
Suspension Bolts
Mounting the Indoor Unit
Air Panel
(1) Mounting the nuts and washers to the suspension bolts.
Insert
(100 to 150kg)
Concrete
* Put the washer so that the surface with insulation can faces downwards.
(2) Lift the Indoor Unit by hoist, and do not put any force on the drain pan.
(3) Secure the indoor unit using the nuts, washers.
If a false ceiling has already benn installed, complete all piping and wiring work
W-Nut (Field Supplied)
inside the ceiling before hooking-up the indoor unit.
Washer (Accessary)
THE CHOICE OF MOUNTING SITE
O
The unit should be mounted at stable, non-vibratory location which can
provide full support to the unit.
O
No nearby heat source and no obstruction near the air outlet is allowed.
O
The clearance distances from top, right and left are speciÀ ed in À gure below.
O
The location must be convenient for water drainage and pipe connection with
the Outdoor unit.
O
Knife
O
Saw
O
To avoid interference from noise please place the unit and its remote controller
4mm)
at least 1m from the radio, television and inverter type Á uorescent lamp.
O
To avoid any error in signal transmission from the remote controller, please put
the controller far away from high-frequency machines and high-power wireless
Flare Tool
systems.
O
The installation height of indoor unit must be 2.3m or more.
Names of Indoor Components
Paper Pattern
1
(Carton Board)
Level Scaler
(Cut and Take
2
Out it from the
Carton Board)
Cross Recessed
Head Screws (M6)
3
Washer with Insulation
Material (M10)
4
Washer (M10)
5
Drain Hose
6
Hose Clamp
7
Insulation (22iD)
8
Insulation (28ID)
9
Cord Clamp
10
Cord Clamp
11
Packing
(5Tx50x200)
12
Packing
(5Tx270x270)
13
Remote Controller
14
Screw for holder of
Remote Controller
15
Liquid Pipe Connection
Gas Pipe Connection
Drain Pipe Connection
Wiring Hole (ø 32.5 Hole)
(for Spare)
Wiring Hole (30x30)
(for Cable)
Fig. 4 Indoor Unit and Air Panel
Suspension Bolt (Field Supplied)
Nut (Field Supplied)
4 *Washer with Insulation (Accessary)
Suspension Blacket (Attaced Indoor Unit)
5 *Washer (Accessary)
Nut (Field Supplied)
Surface of Ceiling
Fig. 5 Mounting Nuts and Washers
Suspension Bolt
Suspension Bracket
Drain Pan
Fig. 6 Mounting the Indoor Unit
NOTE
(Please note the following matters and obtain permission from customer before installation).
WARNING
!
O
The Outdoor unit must be mounted at a location which can support heavy weight.
Otherwise, noise and vibration will increase.
CAUTION
!
O
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be
good and clear of obstruction.
O
The air blown out of the unit should not point directly to animals or plants.
O
The clearances of the unit from top, left, right and front are speciÀ ed in À gure
below. At least 3 of the above sides must be open air.
O
Be sure that the hot air blown out of the unit and noise do not disturb the
neighbourhood.
O
Do not install at a location where there is Á ammable gas, steam, oil and smoke.
O
The location must be convenient for water drainage.
O
Place the Outdoor unit and its connecting cord at least 1m away from the antenna
or signal line of television, radio or telephone. This is to avoid noise interference.
O
Do not install outdoor unit facing strong wind direction. It may damage the fan
motor.
Figure showing the installation of Indoor Unit
CAUTION
!
Air inlet
Air
Air
1000 mm
1000 mm
outlet
outlet
or more
or more
The
installtion
height of indoor
unit must be 2.3m
or more.
Air inlet
Air
Air
outlet
1000 mm
1000 mm
outlet
or more
or more
Dimension of Mounting Stand
of the outdoor unit
(unit : mm)
Mounting Stand
Other optional parts for display panel
& wireless remote control SPX-RCK4
No.
Item
Quantity
Display panel
1
1
Above 100mm
Panel installation plate
1
2
1
Above 500mm
Panel cover
3
Remote controller
1
4
(wireless)
Names of Outdoor Components
Holder for remote control
1
5
No.
3.1 x 16 screw
2
6
Bush
16
Bush
17
Drain Pipe
18
Adjusting the Space between Indoor Unit and False Ceiling Opening
Check the level of the drain pan using a water level to avoid incorrect opera-
O
tion of the drain discharge mechanism in the indoor unit. The drain piping
side of the indoor unit must be approximately 5mm lower than the other part.
Tighten the nuts of the suspension brackets after the adjustment is completed.
O
Apply LOCK-TIGHT paint* to the bolts and nuts in order to prevent them
from loosening. If not done, abnormal noises or sounds may occur and the
indoor unit may fall down.
LOCK-TIGHT paint*: Paint the lock bolts and nuts. Adjust the indoor unit to the
correct position while checking with the checking scales (factory-supplied).
(1) Pattern Board for installation is printed on the packing.
Cut off the checking scale for dimension of opening from packing.
Checking Scale for
Dimension of Opening
Packing
(Corrugated Board)
(2) Adjust the position of indoor unit, as shown below by using checking scale.
10 to 35
Surface of Flange
Indoor Unit (Viewed from Bottom Side)
(a) For Ceiling already Completed with Panels
Attach the scale to the
bottom side of the unit
Checking Scale for
Dimension of Opening
(b) Ceiling Not Completed with Panels yet
Pattern Paper
for Installation
Dimension for
Opening
Indoor unit
Surface of Ceiling
Installation Details for Air Panel
The details of installation work for air panel shall be according to the Instal-
O
lation Manual for Air Panel.
Check to ensure that the connection of connectors between the indoor unit
O
and the air panel.
WARNING
!
CAUTION
!
!
CAUTION
In case the pipe lenght is more than 5m, add refrigerant
R22 at 35 gram per every meter exceeds. However,
pipe lenght shall not exceed 50m.
Be sure to
completely
seal any
gap with
putty.
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufÀ cient, please
use commercial products).
O
The difference in
height between the
indoor and outdoor
unit should be kept
below 30m.
Above 100mm
O
Above 200mm
The connecting
pipe, no matter big
Above 50mm when
give clearance
installed on the
or small, should
as wide as
ceiling of balcony
all be insulated
possible
with insulation pipe
and then wrapped
with vinyl tape.
(The insulator will
deteriorate if it is
not wrapped with
tape).
Above 200mm
Drain Pipe
Must be installed
seperately.
Item
Qty
Insulate indoor part
of pipe to prevent
condensation.
!
CAUTION
Pattern Board
for installation
Slub
10 to 35
Indoor Unit
Surface of Ceiling
Attach the scale to the
face of ceiling
Adjust the height of the ceiling
and the unit at each corner.
Check the dimension of opening
at each side
Dimension for
Opening
Suspension Bolt
Screw (M6)
Pattern Board
for Installation

Advertisement

loading

Summary of Contents for Hitachi RCI-30MH1

  • Page 1 CAUTION CAUTION HITACHI CEILING CASSETTE-UNIT AIR No nearby heat source and no obstruction near the air outlet is allowed. Do not expose the unit under direct sunshine or rain. Besides, ventilation must be Tools Needed For Installation Work The clearance distances from top, right and left are speciÀ...
  • Page 2 Connecting the pipe Drain Piping Connecting the pipe to the indoor unit CAUTION Remove the Á are nut and seal cap. Do not create an upper-slope or rise for the drain piping, since drain water can Á ow back to the indoor unit By loosening the Á...
  • Page 3 Installation of wired remote controller (a) Connection to the electrical box; Wiring installation illustrations Remove the cover of electric box Wall recessed wiring installation (Supplied) Inside top wiring installation (Alternative) Connect the connector of wired remote controller to CN17 Assemble back the cover of electrical box When connecting the wires via the wall’s recessed slot;...
  • Page 4 Preparation of Pipe Removal Of Air From The Pipe And Gas Leakage Inspection Please face this side Please mount the outdoor (suction side) of the u n i t o n s t a b l e g r o u n d unit to the wall.