Electronic Expansion Valve - Hitachi RCI Service Manual

Indoor units system free series & complementary systems
Table of Contents

Advertisement

11 Electrical checks of the
main parts

11.2 Electronic expansion valve

1
Check that the voltage of the valve ranges between 12Vdc
±1.2V.
2
Use a multimeter to check the coil resistance (per phase). This
ranges between 150 Ω±10% at an ambient temperature of 20°.
3
Check the number of pulses per second. This ranges between
100Ω ± 250 pulses per second (the width between pulses is
greater than 3 mm ) on activating phase 2.
4
Check that the valve flow is reversible.
5
When the valve is fully open and in heating process, check that
the temperature of the liquid in the piping increases. If not, this
indicates a fault.
6
When the valve is slightly open or fully open, check that the
temperature of the freeze protection thermistor is higher than
the suction temperature. If not, this indicates a fault.