5 Control system

5.1 Device control system

Purpose of control
Frequency control is determined with
the following parameters:
Compressor control frequency
with Inverter
Degree of opening of the
outdoor unit expansion valve
The control range for the degree of
opening of the expansion valve is
Degree of opening of the
determined to optimise the difference
indoor unit expansion valve
in temperature of the I.U. gas pipe
(Tg) - the temperature of the I.U.
liquid piping (Tl).
The fan speed operates to control the
stabilisation of the O.U. liquid pipe
Outdoor fan
temperature (Te); (Te) stabilisation
control
4-way valve (RVR)
Solenoid
valve
(SVS)
Enabled
(Balanced pressure valve)
(4-10)H(V)RNSE
High/low pressure balance
I.U.: indoor unit.
Tc/Te: condensing temperature / evaporating temperature.
Td: Discharge temperature.
Tl: liquid temperature.
Tg: gas temperature.
Cap: capacity.
160
SMGB0063 rev. 1 - 10/2010
Cooling operation
Difference between the air inlet
temperature and the set air
temperature.
Calculate the width of the
change using the amount of the
change.
Fully open
Off
on
starting
Control by the indoor expansion
valve (2-3 HVRN(1)(S)
SVA
activation
before
the
compressor
is
started
(4-10)H(V)RNSE
Use
Heating operation
Frequency control is determined with
the following parameters:
Difference between the air inlet
temperature and the set air
temperature.
Calculate the width of the change
using the amount of the change.
The control range for the degree of
opening of the expansion valve is
determined
to
optimise
temperature
at
the
top
of
compressor.
Degree of opening specified at the
start
of
normal
control.
Then
controlled to optimise the temperature
of the I.U. liquid pipe (Tl).
The fan speed is controlled in line with
the temperature of the O.U. liquid pipe
and the temperature at the top of the
compressor.
On
Enabled on starting (4-10)H(V)RNSE
Control by the outdoor expansion
valve (2-3 HVRN(1)(S)
SVA
activation
before
compressor
is
started
(4-10)H(V)RNSE
Defrost mode
Fixed frequency (stop the compressor
for 30 s. once defrost is complete).
the
Fully open
the
Specified
degrees
of
controlled by the temperature at the
top of the compressor. (Td).
Fan stoppage.
Off
Enabled by defrost
the
opening