3 Piping work and
refrigerant charge
Connection on the right-hand side
1
Insert the drain hose in the clamp "A".
2
Push the drain hose towards the boss until it reaches the end of the pan.
3
Tighten the screw on the wire clamp to secure the pipe around the drain connection without causing water leaks.
4
Insulate the drain hose around the wire clamp to avoid condensation.
5
Insert the drain pipe into the drain hose and secure it using the wire clamp "B".
Connection on the left-hand side
1
Remove the plug from the drain hose by cutting the securing clip.
2
Remove the insulating material.
3
Remove the drain plug and insert the pipe into the wire clamp.
4
Insert the drain plug into the right-hand boss using a screwdriver.
5
Seal the connection using waterproof chloride sealing material and secure with the pin.
96
SMGB0063 rev. 1 - 10/2010
Clamp A
Drain pipe
Clamp B
Drain pipe
Fan
Drainage
Drainage plug
Wire clamp
Insulating plug
Drainage plug
Drainage plug
Screwdriver
Drainage
Insulation
Fan motor
Drainage connection
Unit