Hitachi RCI Service Manual page 103

Indoor units system free series & complementary systems
Table of Contents

Advertisement

3 Piping work and
refrigerant charge
¿
Drain pipe installation
The correct position for the drain hose connection is shown below.
Prepare a polyvinyl chloride (PVC) pipe with an outer diameter of
32 mm.
Secure the pipe with the clamp and adhesive supplied.
The drain hose must have a gradient of 1% (1/100) to 4% (1/25).
Consider the following sizes: a + b + c ≤ 780 mm.
C A U T I O N
Do not apply adhesive between the drain hose connection and the drain hose.
Do not apply too much force when making the drain hose connection as this could damage it.
Do not use bent or twisted drain pipes as these will cause water leaks.
Then insulate the drain hose appropriately.
91
SMGB0063 rev. 1 - 10/2010
Drain pipe connection
Clamp (accessory)
Do not use adhesive
Clamp (accessory)
Do not use adhesive
Drainage pipe
connection
PVC pipe Ø 32
(field-supplied)
Use PVC adhesive
Drainage pipe
(accessory)
3
4% (1/25) - 1% (1/100)
Drain pipe (accessory)
Clamp (accessory)
Insulation
(field-supplied)