8.3 Procedure for checking fan motors in indoor units

Name and abbreviation of the cable colours used:
Black
Brown
BLK
BRN
Power
Indoor units
output
RCI-1.0FSN3
RCI-1.5FSN3
RCI-2.0FSN3
RCI-2.5FSN3
RCI-3.0FSN3
RCI-4.0FSN3
RCI-5.0FSN3
127 W
RCI-6.0FSN3
RCI-1.0FSN3Ei
RCI-1.5FSN3Ei
RCI-2.0FSN3Ei
RCI-3.0FSN3Ei
RCI-4.0FSN3Ei
RCI-5.0FSN3Ei
108 W
RCI-6.0FSN3Ei
RCIM-0.8FSN2
RCIM-1.0FSN2
RCIM-1.5FSN2
RCIM-2.0FSN2
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.0FSN2
RCD-2.5FSN2
RCD-3.0FSN2
RCD-4.0FSN2
35 W x 2
RCD-5.0FSN2
55 W x 2
256
SMGB0077 rev.0 - 01/2013
Red
Yellow
RED
YEL
Wiring diagram
57 W
DC motor
DC MOTOR
56 W
DC motor
DC motor
52 W
DC motor
35 W
55 W
Green
Blue
GRN
BLU
Cable no.
BLK1-3RED
RED3-5WHT
BLK1-3RED
RED3-5WHT
BLK1-3RED
RED3-5WHT
BLK1-3RED
RED3-5WHT
Grey
Orange
White
GRY
ORN
WHT
Resistance (Ω)
159.00
92.00
to 20 °C
70.90
81.70
to 20 °C
159.00
92.00
to 20 °C
70.90
81.70
to 20 °C