Test run should be performed according to "Installation & Maintenance Manual" of the outdoor unit or
wired remote controller.
WARNING
!
Do not operate the system until all need to add a table with the checks to be made.
(a) Check to ensure that the electrical resistance is more than 1 megohm, by measuring the resistance
between ground and the terminal of the electrical parts. If not, do not operate the system until the
electrical leakage is found and repaired.
(b) Check to ensure that the stop valves of the outdoor unit are fully opened, and then start the system.
(c) Check to ensure that the switch on the main power source has been ON for more than 12 hours, to
warm the compressor oil by the crankcase heater.
Pay attention to the following items while the system is running.
(a) Do not touch any of the parts by hand at the discharge gas side, since the compressor chamber and
the pipes at the discharge side are heated higher than 90°C.
(b) DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH (ES). It will cause a serious accident.

9. Safety and Control Device Setting

Indoor Unit
For Control Circuit Fuse Capacity
Freeze Protection Thermostat
Thermostat Differential

10. Common

10.1 Field Minimum Wire Sizes for Power Source

WARNING
!
Use the ELB(Electric Leakage Breaker) which is above medium reaction speed (residual-current circuit
breaker, action time of 0.1s or less). Otherwise, it may lead to electric shock or fire.
Run the cables through an appropriately sized conduit completely sealing the openings on either
ends.
Model
Power Source
PPFC-2.0UFA1NQ
PPFC-2.5UFA1NQ
PPFC-3.0UFA1NQ
PPFC-4.0UFA1NQ
PPFC-5.0UFA1NQ
PPFC-6.0UFA1NQ
NOTES:
Follow local codes and regulations when selecting field wires.
The wire sizes marked with *1 in the above table are selected at the maximum current of the unit
according to the European Standard, IEC 60335-1. Use the wires which are not lighter than the
ordinary tough rubber sheathed flexible cord (code designation H05RR-F) or ordinary polychloroprene
sheathed flexible cord (code designation H05RN-F) when get power from outside.
Model
Cut-Out
Cut-In
Field Minimum Wire Sizes for Power Source
Maximum Current
(A)
0.43
0.61
0.56
220-240V
~50Hz
1.02
1.02
1.40
PPFC-(2.0-6.0)UFA1NQ
A
°C
°C
°C
Power Cord Size
*1
IEC 60335-1
2
2.5mm
-19-
8. Test Run
5
0
14
2
Transmitting Cable Size
*1
IEC 60335-1
2