Local and remote control

The adjustable frequency drive can be operated man-
ually or remotely. The following is a list of the functions/
If parameter 002 is set to Local [1]:
On the LCP, the following keys can be used for local control:
Key:
[STOP]
[JOG]
[RESET]
[FWD/REV]
Set parameter 013 for LCP control and open loop [1] or LCP control as parameter 100 [3]:
1. Local reference is set in parameter 003; can be changed via the "+/-" keys.
2. Reversing can be effected by means of the [FWD/REV] key.
Set parameter 013 for LCP digital control and open loop [2] or LCP digital control as parameter 100 [4]:
For the above parameter setting, it is now possible to
control the adjustable frequency drive as follows:
Digital inputs:
1.
Local reference set in parameter 003 can be
changed via the "+/-" keys.
2.
Reset via digital terminal 16, 17, 29, 32 or 33.
3.
Stop inverse via digital terminal 16, 17, 27,
29, 32 or 33.
4.
Choice of Setup, lsb via digital terminal 16,
29 or 32.
5.
Choice of Setup, msb via digital terminal 17,
29 or 33.
6.
Ramp 2 via digital terminal 16, 17, 29, 32 or
33.
7.
Quick-stop via digital terminal 27.
8.
DC braking via digital terminal 27.
If parameter 002 is set to Remote control [0]:
Key:
[STOP]
[JOG]
[RESET]
188
Parameter:
014
015
017
016
Parameter:
014
015
017
®
VLT
5000 Series
commands given via the control panel, the digital in-
puts or the serial communication port in the two situa-
tions (modes).
Data value:
[1] Enable
[1] Enable
[1] Enable
[1] Enable
9.
Reset and motor coasting stop via digital ter-
minal 27.
10.
Motor coasting stop via digital terminal 27.
11.
Reversing via digital terminal 19.
12.
Choice of Setup, msb/speed up via digital
terminal 32.
13.
Choice of Setup, lsb/speed down via digital
terminal 33.
The serial communication port:
1.
Ramp 2
2.
Reset
3.
Choice of Setup, lsb
4.
Choice of Setup, msb
5.
Relay 01
6.
Relay 04
Data value:
[1]
[1]
[1]
MG.51.C5.22 - VLT
is a registered Danfoss trademark.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT 5000 Series and is the answer not in the manual?

Questions and answers

Table of Contents