7.
Press the [OK] key.
8.
Parameter 620 is automatically set to Normal
operation.
If a test fails, the adjustable frequency drive will move
into an infinite loop. Replace control card.
Test plugs:
Inialisation [3] is selected if the factory setting of the unit
is desired without resetting parameters 500, 501 + 600
- 605 + 615 - 617.
NOTE
The motor must be stopped before initial-
isation can be carried out.
Parameter no.
621
622
623
624
625
626
627
628
629
630
631
Function:
The key data of the unit can be read out via the display
or the serial communication port.
Description of choice:
VLT type , parameter 621:
152
Description
Nameplate
VLT type
Power section
VLT ordering number
Software version number
LCP identification number
Database identification number
Power section identification number
Application option type
Application option ordering number
Communication option type
Communication option ordering number
®
VLT
5000 Series
Procedure for initializing:
1.
Select Initialisation.
2.
Press the [OK] key.
3.
Cut off the mains supply and wait for the light
in the display to go out.
4.
Connect to mains.
Manual initialisation can be carried out by holding
down three keys at the same time as the mains voltage
is connected. Manual initialisation sets all parameters
to the factory setting, except 600-605. The procedure
for manual initialisation is as follows:
1.
Disconnect the mains voltage and wait for the
light in the display to disappear.
2.
Hold down [DISPLAY/STATUS]+[MENU]+
[OK] while at the same time connecting the
mains supply. The display will now read
MANUAL INITIALIZE.
3.
When the display reads UNIT READY, the
adjustable frequency drive has been initial-
ized.
(VLT TYPE)
(POWER SECTION)
(VLT ORDERING NO)
(SOFTWARE VERSION)
(LCP ID NO)
(PARAM DB ID)
(POWER UNIT DB ID)
(APP. OPTION)
(APP. ORDER NO)
(COM. OPTION)
(COM. ORDER NO)
VLT Type indicates the unit size and basic function
concerned.
For example: VLT 5008 380-500 V.
Power section, parameter 622:
The power section states the given power section be-
ing used.
For example: Extended with brake.
MG.51.C5.22 - VLT
is a registered Danfoss trademark.