Switching on the input
Switching on the input depends on the AC line voltage
in question and on whether quick discharge of the in-
termediate capacitor has been selected. The table
below states the waiting time between cut-ins.
AC line volt-
380 V
415 V
460 V
age
Without
48 s
65 s
89 s
quick dis-
charge
With quick
74 s
95 s
123 s
discharge
Acoustic noise
The acoustic interference from the adjustable frequen-
cy drive comes from two sources:
1.
DC intermediate circuit coils.
2.
Integral fan.
Below are the typical values measured at a distance
of 1 m from the unit at full load:
VLT 5001-5006 200 - 240 V, VLT 5001-5011 380 -
500 V
IP 20 / NEMA 1 units:
50 dB(A)
IP 54 / NEMA 12 units:
62 dB(A)
VLT 5008-5027 200 - 240 V, VLT 5016-5102 380 -
500 V
IP 20 / NEMA 1 units:
61 dB(A)
IP 20 / NEMA 1 unit (VLT
67 dB(A)
5062-5102):
IP 54 / NEMA 12 units:
66 dB(A)
VLT 5032-5052 / 200 - 240 V
IP 20 / NEMA 1 units:
70 dB(A)
IP 54 / NEMA 12 units:
65 dB(A)
VLT 5122-5302 / 380 - 500 V
IP 21 / NEMA 1 units:
73 dB(A)
IP 54 / NEMA 12 units:
73 dB(A)
VLT 5352 / 380 - 500 V
IP 00 and IP 21/ NEMA 1
80 dB(A)
units:
IP 54 / NEMA 12 units:
80 dB(A)
VLT 5452-5552 / 380 - 500 V
All enclosure types:
83 dB(A)
VLT 5001-5011 / 525 - 600 V
IP 20 / NEMA 1 units:
62 dB(A)
MG.51.C5.22 - VLT
is a registered Danfoss trademark.
VLT 5016-5062 / 525 - 600 V
IP 20 / NEMA 1 units:
VLT 5042-5352 / 525 - 690 V
IP 21/NEMA 1 units:
IP 54 units:
VLT 5402 / 525 - 690 V
500 V
690 V
All enclosure types:
117 s
120 s
VLT 5502-5602 / 525 - 690 V
All enclosure types:
158 s
Measured 1 meter from the unit at full load.
®
VLT
5000 Series
66 dB(A)
74 dB(A)
74 dB(A)
80 dB(A)
83 dB(A)
211