Fuses - Danfoss VLT 5000 Series Instruction Manual

Hide thumbs Also See for VLT 5000 Series:
Table of Contents

Advertisement

Fuses

UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
VLT
Bussmann
5001
KTN-R10
5002
KTN-R10
5003
KTN-R25
5004
KTN-R20
5005
KTN-R25
5006
KTN-R30
5008
KTN-R50
5011
KTN-R60
5016
KTN-R85
5022
KTN-R125
5027
KTN-R125
5032
KTN-R150
5042
KTN-R200
5052
KTN-R250
380-500 V
Bussmann
5001
KTS-R6
5002
KTS-R6
5003
KTS-R10
5004
KTS-R10
5005
KTS-R15
5006
KTS-R20
5008
KTS-R25
5011
KTS-R30
5016
KTS-R40
5022
KTS-R50
5027
KTS-R60
5032
KTS-R80
5042
KTS-R100
5052
KTS-R125
5062
KTS-R150
5072
FWH-220
5102
FWH-250
5122*
FWH-300/170M3017
5152*
FWH-350/170M3018
5202*
FWH-400/170M4012
5252*
FWH-500/170M4014
5302*
FWH-600/170M4016
5352
170M4017
5452
170M6013
5502
170M6013
5552
170M6013
* Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, with rating plugs listed below can be used to meet UL-
requirements:
5122
rating plug No.
5152
rating plug No.
5202
rating plug No.
5252
rating plug No.
5302
rating plug No.
MG.51.C5.22 - VLT
is a registered Danfoss trademark.
SIBA
5017906-010
5017906-010
5017906-016
5017906-020
5017906-025
5012406-032
5014006-050
5014006-063
5014006-080
2028220-125
2028220-125
2028220-160
2028220-200
2028220-250
SIBA
5017906-006
5017906-006
5017906-010
5017906-010
5017906-016
5017906-020
5017906-025
5012406-032
5012406-040
5014006-050
5014006-063
2028220-100
2028220-125
2028220-125
2028220-160
2028220-200
2028220-250
2028220-315
2028220-315
206xx32-400
206xx32-500
206xx32-600
2061032,700
2063032,900
2063032,900
2063032,900
SRPK800 A 300
SRPK800 A 400
SRPK800 A 400
SRPK800 A 500
SRPK800 A 600
®
VLT
5000 Series
Littel fuse
Ferraz-Shawmut
KLN-R10
ATM-R10 or A2K-10R
KLN-R10
ATM-R10 or A2K-10R
KLN-R15
ATM-R15 or A2K-15R
KLN-R20
ATM-R20 or A2K-20R
KLN-R25
ATM-R25 or A2K-25R
KLN-R30
ATM-R30 or A2K-30R
KLN-R50
A2K-50R
KLN-R60
A2K-60R
KLN-R80
A2K-80R
KLN-R125
A2K-125R
KLN-R125
A2K-125R
L25S-150
A25X-150
L25S-200
A25X-200
L25S-250
A25X-250
Littel fuse
Ferraz-Shawmut
KLS-R6
ATM-R6 or A6K-6R
KLS-R6
ATM-R6 or A6K-6R
KLS-R10
ATM-R10 or A6K-10R
KLS-R10
ATM-R10 or A6K-10R
KLS-R16
ATM-R16 or A6K-16R
KLS-R20
ATM-R20 or A6K-20R
KLS-R25
ATM-R25 or A6K-25R
KLS-R30
A6K-30R
KLS-R40
A6K-40R
KLS-R50
A6K-50R
KLS-R60
A6K-60R
KLS-R80
A6K-180R
KLS-R100
A6K-100R
KLS-R125
A6K-125R
KLS-R150
A6K-150R
L50S-225
A50-P225
L50S-250
A50-P250
L50S-300
A50-P300
L50S-350
A50-P350
L50S-400
A50-P400
L50S-500
A50-P500
L50S-600
A50-P600
6.9URD31D08A0700
6.9URD33D08A0900
6.9URD33D08A0900
6.9URD33D08A0900
33