CPU364

CPU Type
Total Baseplates per System
Load Required from Power Supply 1.51 Amps from +5 VDC supply
Processor Speed
Processor Type
Ethernet fuse, replaceable
Operating temperature
Typical Scan Rate
User Memory (total)
Discrete Input Points - %I
Discrete Output Points - %Q
Discrete Global Memory - %G
Internal Coils - %M
Output (Temporary) Coils - %T
System Status References - %S
Register Memory - %R
Analog Inputs - %AI
Analog Outputs - %AQ
System Registers (
for reference table
viewing only; cannot be referenced in logic
program)
Timers/Counters
Shift Registers
Built-in Serial Ports
Communications
Override
Battery Backed Clock
Interrupt Support
Type of Memory Storage
PCM/CCM Compatibility
Floating Point Math Support
Note:
GFK-0356Q
Chapter 5 CPUs

Catalog Number IC693CPU364

Single slot CPU module with embedded Ethernet Interface
8 (CPU baseplate + 7 expansion and/or remote)
25 MegaHertz
80386EX
2.69x2.69x6.1 mm, 125V, 1A, slow acting
0 to 60 degrees C (32 to 140 degrees F) ambient
0.22 milliseconds per 1K of logic (boolean contacts)
240K Bytes. Note: Actual size of available user program memory
depends on the amounts configured for %R, %AI, and %AQ
configurable word memory types (see below).
2,048
2,048
1,280 bits
4,096 bits
256 bits
128 bits (%S, %SA, %SB, %SC - 32 bits each)
Configurable in 128 word increments from 128 to 16,384 words
with Logicmaster and from 128 to 32,640 words with Control
version 2.2.
Configurable in 128 word increments from 128 to 16,384 words
with Logicmaster and from 128 to 32,640 words with Control
version 2.2.
Configurable in 128 word increments from 128 to 16,384 words
with Logicmaster and from 128 to 32,640 words with Control
version 2.2.
28 words (%SR)
>2,000
Yes
1 (uses connector on PLC Power Supply). Supports SNP/SNPX
slave. Requires CMM module for SNP/SNP-X master, RTU slave,
or CCM; PCM module for RTU master support.
Ethernet (internal) - AAUI or 10BASE-T. AAUI requires
external transceiver. 10BASE-T is direct.
Ethernet (additional) - Supports Ethernet option modules.
LAN-Requires option modules for Genius, Profibus, FIP.
Yes
Yes
Supports the periodic subroutine feature.
RAM and Flash
Yes
Yes, firmware-based.
On some early modules, the LED labeled "PS PORT" may say "SNP" instead; otherwise,
the modules are identical.
5
SNP
EOK
LAN
CPU 364
STAT
ON
OFF
ETHERNET
RESTART
PORT 1
RS_232
AAUI
10BASE T
FRAME
5-39