E
*
*
E-2
Series 90-30 PLC Installation and Hardware Manual – August 2002
Connectors
The Isolator provides two connectors, one 15 pin male D-type (PL1) and one
15 pin female D-type (PL2).
RS-485 Connectors
Pin
Pin Name
PL1
1
SHLD
2
NC
3
NC
4
NC
5
5V
6
CTS (A')
7
0V
8
RTS (B)
9
NC
10
SD (A)
11
SD (B)
12
RD (A')
13
RD (B')
14
CTS (B')
15
RTS (A)
Pin
Pin Name
PL2
1
NC
2
NC
3
NC
4
NC
5
5V
6
RTS (A)
7
0V
8
CTS (B')
9
RT
10
RD (A')
11
RD (B')
12
SD (A)
13
SD (B)
14
RTS (B)
15
CTS (A')
Use the terminating resistor if the Port Isolator is used in port-to-port mode or at the end of a multi-drop
configuration. To terminate the RD balanced line, place a jumper wire from pin 9 to pin 10.
A denotes – and B denotes +. A and B denote outputs and A' and B' denote inputs.
Pin Type
Description
-
Chassis Ground
-
-
-
-
+5V power
In
Clear to send -
-
Signal Ground
Out
Request to send +
-
Out
Send data -
Out
Send data +
In
Read data -
In
Read data +
In
Clear to send +
Out
Request to send -
Pin Type
Description
-
-
-
-
-
+5V power
Out
Request to send -
-
Signal Ground
In
Clear to send +
-
Terminating Resistor*
In
Read data -
In
Read data +
Out
Send data -
Out
Send data +
Out
Request to send +
In
Clear to send -
GFK-0356Q