DVM Specifications
Table 7-1. IC693DVM300 Specifications
any power from PLC backplane.)
Fuses
GFK-0356Q
Chapter 7 Input/Output Modules
Outputs (Channels) per Module
Isolation
Nominal Output Voltage
Power Supply for Output Channels
Output Current
Output Voltage Drop (fully loaded)
Off state leakage current
Turn-on response time
Turn-off response time
Output protection (per channel)
Input Voltage
Logic 1 Level
Input Current
Input protection
AUXILIARY POWER SUPPLY OUTPUTS
Voltage and Current
Isolation
MODULE POWER REQUIREMENTS
Power Consumption (Does not consume
Input Voltage
Quantity - Module control power.
Quantity 4 - One for each output. 2 Amps. Littlefuse 239002.
OUTPUT CHARACTERISTICS
4
2500 Vrms (optical isolation)
24 VDC
26 VDC nominal, 2 VDC minimum, 35 VDC
maximum
.6 Amps maximum per channel
6.4 Amps maximum total per module
0.32 VDC
26 ∝A at 26 VDC operating voltage
< ∝S with resistive load
< ∝S with resistive load
Reversed-biased zener diode for free-wheeling
inductive current. Also 36 Volt transorb for
ESD and surge protection.
INPUT CHARACTERISTICS
5 VDC (TTL) nominal, 2Vdc Maximum
Logic : V > 3.5 VDC
Logic 0: V < 0.7 VDC
3.8 mA nominal
3.3 Volt transorb
+ 5 VDC @ 0.3A and - 5 VDC @ 0.2A
Not isolated
5.6 Watts (with all outputs on) from external
supply connected to terminals and 2 (does
not include power consumed by outputs)
+26 VDC nominal, 35 VDC maximum
continuous
Amp. Buss GDB- A.