GE 90-30 PLC Series Installation And Hardware Manual page 85

Hide thumbs Also See for 90-30 PLC Series:
Table of Contents

Advertisement

3
Baseplate Mounting Dimensions
Note:
Series 90-30 PLC baseplates are designed to be panel mounted. Each baseplate has standard
attachment flanges for mounting on an electrical panel. Baseplate dimensions and proper spacing
requirements for installation purposes for both the 5 and 10-slot baseplates with embedded CPU
(Models 311 and Model 313 are 5-slot baseplates; Model 323 is a 10-slot baseplate), and the 5 and
10-slot baseplates for Modular CPUs are shown in figures 3-1 through 3-4.
Embedded CPU (311, 313, and 323) Baseplate Dimensions
Baseplate dimensions and spacing requirements for installation for Models 311, 313, and 323
baseplates are shown below.
Figure 3-14.
3-16
Series 90-30 PLC Installation and Hardware Manual – August 2002
Series 90-30 PLCs must be mounted in a protective enclosure. The enclosure should be
capable of properly dissipating the heat produced by all of the devices mounted inside it.
For details on calculating heat dissipation, refer to Appendix F.
All 5-slot baseplates have the same mounting dimensions and all 10-slot
baseplates have the same mounting dimensions. Baseplates must be mounted in
the orientation as shown in the following figures for proper cooling.
10.43
4.00
*
(102)
(265)
9.84
(250)
8.60
(218)
POWER
SUPPLY
3.54
(90)
FRONT VIEW
.79
(20)
*
ALLOWANCE FOR COOLING
Model 311 and 313 5-Slot Baseplate Dimensions and Spacing Requirements
Note
DIMENSIONS IN INCHES,
4.00
*
MILLIMETERS ARE IN PARENTHESIS
(102)
4.00
*
(102)
REMOVABLE
I/O
TERMINAL
BLOCK
.20 DIA.
(5.08)
5.12
(TYPICAL)
(130)
HINGED
DOOR
4.00
*
(102)
5.59
(142)
SIDE VIEW
GFK-0356Q