5
Series 90-30 CPU Capacities
The following table describes the maximum capacities and operating features for the Series 90-30
PLC CPU models. For State Logic CPUs, see "System Specifications for Series 90-30 State Logic
CPUs" in Chapter 9.
Table 5-3. Series 90-30 CPU Capacities
CPU
Model
CPU311
CPU313
CPU323
CPU331
CPU340
CPU341
CPU350
CPU351
CPU352
CPU360
CPU363
CPU364
CPU374
1
Maximum of 160 combined I + O points.
2
Maximum of 320 combined I + O points.
3 Configurable from 128 to 32,640 words, in 128 word increments.
4 Depends on assigned values for configurable word memory (%R, %AQ, %AI). Maximum is 240K Bytes.
5 CPU352 and CPU374 have hardware-based floating point math. Other CPUs have firmware-based floating point math.
User Memory Addresses (References)
Data in the Series 90-30 PLC programs is referenced by its memory address. A reference indicates
the way that data is stored in the PLC. A reference specifies both a memory type and a precise
location (number) within that memory type. For example:
Difference Between a Memory Address and a Nickname
The % symbol is used to distinguish memory addresses from nicknames. For example, %I17 (or
%I000017) is a memory address. The similar term, I17 (it has no % sign), is viewed by the PLC as
a nickname and could be used with most memory addresses. For example, if you had a motor in
your plant called "Infeed No. 17," and it was commonly referred to as "I17" by the people in your
plant, you might wish to use I17 as the nickname for the output coil (%Q11) that turns on that
motor. You are allowed to do so because the PLC can distinguish between the nickname, I17 (your
nickname for memory address %Q11), and memory address %I17.
5-10
Series 90-30 PLC Installation and Hardware Manual – August 2002
Speed,
(MHz)
Processor
10
80188
10
80188
10
80188
10
80188
20
80C188XL
20
80C188XL
25
80386EX
25
80386EX
25
80386EX
25
80386EX
25
80386EX
25
80386EX
133
586
%I00001
specifies address 1 in input memory.
%R00256
specifies address 256 in register memory.
Input
Output
Register
Points
Points
Memory
1
1
160
160
1K (Bytes)
1
1
160
160
2K (Bytes)
2
2
320
320
2K (Bytes)
512
512
4K (Bytes)
512
512
19.9K (Bytes)
512
512
19.9K (Bytes)
2048
2048
19.9K (Bytes)
2048
2048
Note 3
2048
2048
Note 3
2048
2048
Note 3
2048
2048
Note 3
2048
2048
Note 3
2048
2048
Note 3
User Program
Floating
Memory
Point
(Maximum)
Math
6K (Bytes)
no
12K (Bytes)
no
12K (Bytes)
no
16K (Bytes)
no
32K (Bytes)
no
80K (Bytes)
no
32K (Bytes)
yes
Note 4
yes
5
Note 4
yes
Note 4
yes
Note 4
yes
Note 4
yes
5
Note 4
yes
GFK-0356Q