FIP Bus Interface
The Remote I/O Scanner communicates at a data rate of 1MHz. There are two versions of the FIP
communications standard: FIP and WORLD FIP. A DIP switch on the module is used to select the
version that will be used by the Remote I/O Scanner. (The same communications method will then
be used on both bus cables).
The DIP switch on the module must be set to the FIP position for the Remote I/O Scanner to
communicate with a Series 90-70 PLC.
Module Description
The FIP Remote I/O Scanner is a standard Series 90-30 PLC module that plugs easily into the
backplane of the baseplate.
Figure 8-9. FIP Bus Interface Module
GFK-0356Q
Chapter 8 Option Modules
permits I/O forcing from the Hand-Held Programmer
detects and records input transitions
supports FIP messaging services
responds to an external synchronization signal
can provide blinking or pulsed outputs
can provide input filtering and chatter detection
FIP CH S2
1.0 MHz
C
H
A
N
N
E
L
1
C
H
A
N
N
E
L
2
S
Y
N
C
H
R
O
CD1
TEN1
LEDs
CD2
TEN2
FIP Bus Connectors
Synchro Connector
Lug for Ground Wire