GE 90-30 PLC Series Installation And Hardware Manual page 215

Hide thumbs Also See for 90-30 PLC Series:
Table of Contents

Advertisement

IC693TCM302/303 Temperature Control Modules (TCM)
The Temperature Control Modules (TCM) provides temperature control for up to eight channels.
The two TCM models are identical except for temperature range and resolution ratings (see
comparison table). They have the following features:
Figure 8-22. IC693TCM302/303 Temperature Control Module (TCM)
Connections
Field devices (thermocouples, relays), RTD and external power for output relays are connected to
the module using a pair of plug-in connectors which are supplied with the module. These
connectors have captive screw terminals for ease of connecting field wiring. The signal name for
each terminal is labeled on the module's front cover next to each connector, as shown in the
drawing above. For example, Channel 8 connections are labeled 8+ and 8- on each connector.
Input connections are on the left-hand connector and output connections are on the right-hand
connector.
GFK-0356Q
Chapter 8 Option Modules
Can operate in either open loop or closed loop mode
Each channel has a thermocouple input and a relay output
RTD input
12V common mode voltage capability
Open and reverse thermocouple detection and reporting
Out of tolerance temperature detection and reporting
Power, Run, Fault,
and Short LEDs
Front Cover
RTD Input
Input Connector
P R F S
1
4
Output Status LEDs (1 – 8)
5
8
TCM
RTD
PWR
+ 1/P
+ 0/P
Location of Fuse
(Behind Front Cover)
R-
P+
S-
P-
External Power Input
S+
G
for Output Relays
R
1+
1+
1-
1-
2+
2+
2-
2-
Output Connector
3+
3+
3-
3-
4+
4+
4-
4-
5+
5+
5-
5-
6+
6+
6-
6-
7+
7+
7-
7-
8+
8+
8-
8-
8
8-37