10
Remote baseplates IC693CHS393F (and later( and IC693CHS399E (and later) have a change
inside the baseplate which alleviates the need to remove pin 1 from the mating cable. When using
factory made Wye cable with these baseplates, it is not necessary to remove pin 1 from the cable.
Custom built Wye cables for these baseplates can be made using either Figure 10-20 or Figure 10-
21. Figure 10-21 shows how the factory made Wye cable are made.
CABLE
TO
DOWNSTREAM
RACK
OR
TERMINATION
PLUG
25-PIN
MALE
Metallized Shell
SHIELD DRAIN WIRE
NOTE:
Bold dashed line shows continuous (100%) shielding when metallized shell connectors are plugged together.
Figure 10-20. Current Remote baseplate (IC693CHS393/399) Custom Wye Cable Wiring Diagram
10-30
Series 90-30 PLC Installation and Hardware Manual – August 2002
PIN
DIODT
16
DIODT/
17
DIOCLK
24
DIOCLK/
25
DRSEL
20
21
DRSEL/
12
DRPERR
DRPERR/
13
DRMRUN
8
DRMRUN/
9
DPFRAME
2
DPFRAME/
3
7
0V
NC
FGND
1
25-PIN
FEMAL
Metallized
TWISTED SHIELDED
PAIRS
PIN
16
DIODT
17
DIODT/
24
DIOCLK
25
DIOCLK/
20
DRSEL
DRSEL/
21
REMOTE
DRPERR
12
EXPANSION
DRPERR/
BASEPLATE
13
CONNECTOR
DRMRUN
8
9
DRMRUN/
2
DPFRAME
3
DPFRAME/
7
0V
NC
FGND
1
25-PIN
25-PIN
MALE
FEMALE
Metallized Shell
Metallized Shell
SHIELD DRAIN
CONNECTED
FOR REMOTE BASEPLATES
IC693CHS399E (AND EARLIER REVISIONS OF EACH)
PIN
16
DIODT
DIODT/
17
DIOCLK
24
DIOCLK/
25
DRSEL
20
DRSEL/
21
DRPERR
CABLE
12
FROM
DRPERR/
13
UPSTREAM
DRMRUN
8
RACK
DRMRUN/
9
DPFRAME
2
DPFRAME/
3
7
0V
NC
1
FGND
25-PIN
25-PIN
MALE
FEMALE
Metallized Shell
Metallized Shell
GFK-0356Q