4 HMI

This chapter contains the following information:
HMI keys and functions.
Indications on the display.
Parameter structure.

4.1 HMI-CFW11W G2 HUMAN MACHINE INTERFACE

Using the HMI, it is possible to command the inverter, and to view and set all parameters. It presents a navigation
method similar to that used in cell phones, with the option to access the parameters sequentially or by means of
groups (Menu).
Left soft key: press this key to select the
above highlighted menu feature.
1. Press this key to advance to the next
parameter or to increase a parameter value.
2. Press this key to increase the speed.
3. Press this key to select the previous
group in the parameter groups.
Press this key to define the direction of
rotation for the motor.
Active when:
P0223 = 2 or 3 in LOC and/or
P0226 = 2 or 3 in REM.
Press this key to switch between LOCAL
or REMOTE modes.
Active when:
P0220 = 2 or 3.
Press this key to accelerate the motor to the speed set in P0122 in the time set
for the acceleration ramp.
The motor speed is kept while this key is pressed.
Once this key is released, the motor will stop by following the deceleration ramp.
This function is active when all conditions below are satisfied:
1. Start/Stop = Stop.
2. General Enable = Active.
3. P0225 = 1 in LOC and/or P0228 = 1 in REM.
Battery:
NOTE!
The battery is only necessary to maintain operation of the internal clock when the inverter is de-
energized. In case the battery is low, or not installed on the HMI, the clock time becomes incorrect
and alarm A181 – "Clock with invalid value" will be indicated every time the inverter is turned on.
The life expectation of the battery is of approximately 10 years. Replace the battery, when necessary, by a CR2032
battery.
Figure 4.1: HMI keys
Right soft key: press this key to select the
above highlighted menu feature.
1. Press this key to move back to the
previous parameter or to decrease a
parameter value.
2. Press this key to decrease speed.
3. Press this key to select the next group
in the parameter groups.
Press this key to accelerate the motor in
the time set for the acceleration ramp.
Active when:
P0224 = 0 in LOC or
P0227 = 0 in REM.
Press this key to stop the motor in the time
set for the deceleration ramp.
Active when:
P0224 = 0 in LOC or
P0227 = 0 in REM.
CFW-11W G2 | 4-1
HMI