Installation and Connection
3
Figure 3.37: ICUP shield fastened to the panel
The control rack must be grounded using a flat flexible braid with minimum width of 5 mm and minimum cross-
section of 3 mm² with standard FASTON terminal 6.35 mm (E.g.: TYCO 735075-0 and 180363-2) and lug terminal
M4; see
Figure 3.38 on page
3-33.
Flexible Braid
Figure 3.38: Control rack grounding
The panel door must be grounded with flexible braid.
Figure 3.39: Grounding of the panel door