The Input Rectifier of the CFW-11W G2 can be supplied via contactor or motorized circuit breaker (represented
by K1), and its command must be interlocked with the command of the KPCR pre-charge contactor.
on page 3-15
shows an example of a pre-charge circuit recommended for the CFW-11W G2 inverter, with the
simplified power and control diagrams. The digital relay output DO1 of the CC11 board must be configured with
the "Pre-Charge OK" function (P0275 = 25). This relay must be used to command the pre-charge contactor and
the main contactor (motorized circuit breaker). In addition, the duration of the pre-charge must be timed to protect
the components of the auxiliary circuit (resistors, contactor). This function is performed by a timing relay with on-
delay, represented in
Figure 3.17 on page 3-15