WEG CFW11W G2 Series User Manual page 57

Frequency inverter
Hide thumbs Also See for CFW11W G2 Series:
Table of Contents

Advertisement

Installation and Connection
Drive 4 - Forward/Reverse.
Enabling of the Forward/Reverse function.
Parameters to be set:
Program DI3 to FORWARD.
P0265 = 4.
Program DI4 to REVERSE.
3
P0266 = 5.
When the Forward/Reverse function is programmed, it will be enabled, both in local and remote mode.
At the same time the keys
The direction of rotation is defined by the forward and reverse inputs.
Clockwise rotation for forward and counterclockwise for reverse.
The speed reference can come from any source (like in Drive 3).
3-40 | CFW-11W G2
and
are always disabled (even if P0224 = 0 or P0227 = 0).
Stop/Forward S1
Stop/Reverse S2
Figure 3.47: Connections in XC1 for Drive 4
Conector XC1
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND *
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NF1
DO1
22
C1
(RL1)
23
NA1
24
NF2
DO2
25
C2
(RL2)
26
NA2
27
NF3
DO3
28
C3
(RL3)
29
NA3

Advertisement

Table of Contents
loading