Optional Items and Accessories
ATTENTION!
The UP11W G2 becomes 120 mm higher with the quick couplings in the coolant inlet and outlet fittings.
ATTENTION!
The addition of quick couplings increases de pressure drop in the UP11W G2 by 1,55 bar. Considering
the 20 l/min flow and the composition of 88,5 % of water, 10 % de glycol and 1,5 % of inhibitor CorteC
VpCI-649 in the coolant.

7.1.2 Safety Stop Function

Inverters with the following coding CFW11WG2...O...Y.... See the
3-41.

7.2 ACCESSORIES

The accessories are installed on the inverters easy and quickly using the "Plug and Play" concept. When an
accessory is connected to the slots, the control circuit identifies the model and informs the code of the accessory
connected in P0027 or P0028. The accessory must be installed with the inverter power supply disconnected.
The code and models available of each accessory are presented in
separately and will be shipped in individual packages containing the components and the manuals with detailed
7
instructions for the product installation, operation and programming.
ATTENTION!
Only one module can be used at a time in each slot 1, 2, 3, 4 or 5.
WEG Item
(material
Name
number)
11008162
IOA-01
11008099
IOB-01
11126674
IOC-01
11126730
IOC-02
11820111
IOC-03
11126732
IOE-01
11126735
IOE-02
11126750
IOE-03
11008100
ENC-01
11008101
ENC-02
11008102
RS485-01
11008103
RS232-01
11008104
RS232-02
11008105
CAN/RS485-01
11008106
CAN-01
11045488
PROFIBUS DP-01
11008911
PLC11-01
7-2 | CFW-11W G2
Table 7.1: Accessory models
Description
Control Accessories to Install in Slots 1, 2 and 3
IOA Module: 1 analog 14-bit input in voltage and current; 2 digital inputs; 2
analog 14-bit outputs in voltage and current; 2 open collector digital outputs
IOB Module: 2 isolated analog inputs in voltage and current; 2 digital inputs;
2 isolated analog outputs in voltage and current (same output programming
as the standard CFW-11); 2 open-collector digital outputs
Module with 8 digital inputs and 4 digital relay outputs (use with SoftPLC)
Module with 8 digital inputs and 8 NPN open-collector digital outputs (use
with SoftPLC)
IOC module with 8 digital inputs and 7 PNP open-collector digital outputs
Input module for 5 PTC sensors
Input module for 5 PT100 sensors
Input module for 5 KTY84 sensors
Incremental encoder module, 5 to 12 Vdc, 100 kHz, with repeater of the
encoder signals
Incremental encoder module, 5 to 12 Vdc, 100 kHz
RS-485 serial communication module (Modbus)
RS-232C serial communication module (Modbus)
RS-232C serial communication module with switches to program the
microcontroller flash memory
CAN and RS-485 interface module (CANopen / DeviceNet / Modbus)
CAN interface module (CANopen / DeviceNet)
Profibus DP communication module
PLC module
Section 3.3 SAFETY STOP FUNCTION on page
Table 7.1 on page
7-2. They may be ordered
Identification
Parameters
Slot
P0027 P0028
1
FD--
----
1
FA--
----
1
C1
----
1
C5
----
1
C6
----
1
25--
----
1
23--
----
1
27--
----
2
--C2
----
2
--C2
----
3
----
CE--
3
----
CC--
3
----
CC--
3
----
CA--
3
----
CD--
3
----
C9
1, 2
----
--xx
(1)(3)
and 3