Cooling System - WEG CFW11W G2 Series User Manual

Frequency inverter
Hide thumbs Also See for CFW11W G2 Series:
Table of Contents

Advertisement

3.1.6 Cooling System

Figure 3.14 on page 3-9
shows the details of the coolant inlet and outlet.
Table 3.3 on page 3-9
contains detailed specifications of the UP11W G2 cooling system.
Coolant Inlet Temperature
Fluid Temperature Increase
Coolant Flow
Maximum Flow Allowed
Maximum System Pressure in Relation to
the Atmosphere
Load Loss on the Inverter Heatsink
Coolant Inlet and Outlet Fittings Used on
the Inverter
Note:
1. Considering the 20 l/min flow and the composition of 88,5 % of water, 10 % de glycol and 1,5 % of inhibitor
CorteC VpCI-649 in the coolant.
(DIN 3861 / ISO 8434-1)
Coolant inlet
Coolant outlet
Figure 3.14: Detail of the coolant inlet and outlet
Table 3.3: Cooling system specifications
From 0 ºC to 45 ºC (32 °F to 113 °F) according to the coolant; see
3-12. From 45 ºC to 55 ºC (113 °F to 131 °F) with output current derating
6 °C (43 °F)
(1)
20 l/min
30 l/min
6 bar (600 kPa)
0,84 bar (84 kPa)
(1)
Stainless steel bulkhead fitting for 16 mm tube, M24X1.5 thread and 24° taper (DIN
3861/ISO 8434-1). According to
M24X1.5 thread
Tube Gauge 16 mm
Internal taper of 24°
Figure 3.15: Details of the hydraulic connection on the product
Installation and Connection
Figure 3.15 on page 3-9
3
Table 3.7 on page
CFW-11W G2 | 3-9

Advertisement

Table of Contents