Drive 3 - Run/Stop function with three-wire control.
Enabling of the Run/Stop function with three-wire control.
Parameters to be set:
Program DI3 to START.
P0265 = 6.
Program DI4 to STOP.
P0266 = 7.
Program P0224 = 1 (DIx) in case you wish the 3-wire control in Local mode.
Program P0227 = 1 (DIx) in case you wish the 3-wire control in Remote mode.
Program the Direction of Rotation via DI2.
Program P0223 = 4 for Local Mode or P0226 = 4 for Remote Mode.
S1 and S2 are, respectively, ON (NO contact) and OFF (NC contact) pushbuttons.
The speed reference can be via AI analog input (as in Drive 2), via HMI (as in Drive 1) or another source.
Forward/Reverse
S3 (FWD/REV)
Start S1
Stop S2
Figure 3.46: Connections in XC1 for Drive 3
Installation and Connection