WEG CFW11W G2 Series User Manual page 101

Frequency inverter
Hide thumbs Also See for CFW11W G2 Series:
Table of Contents

Advertisement

Technical Data
Power Supply [V
Rated Output Current [Arms]
Overload Current
[Arms]
Switching Frequency [kHz]
Normal
Duty (ND)
Maximum Motor [cv/kW]
Rated Input Current [Adc]
Dissipated Power
[kW]
Rated Output Current [Arms]
Overload Current
[Arms]
Switching Frequency [kHz]
Heavy
Duty (HD)
Maximum Motor [cv/kW]
Rated Input Current [Adc]
Dissipated Power
[kW]
Note:
(1) Steady state rated current in the following conditions:
- Indicated switching frequency. It is not possible to use the CFW11W G2 inverter with switching frequency of 2.5 kHz, 5 kHz and 10 kHz.
- Ambient temperature around the inverter as specified in
to 55 º C, the output current must be derated by 0,5 % for each º C above the maximum temperature specified.
- Coolant input temperature as specified in
output current must be derated by 1 % for each º C above the maximum temperature specified.
- Coolant flow as specified in
- Air relative humidity: 5 % to 95 % non-condensing.
- Altitude: 1000 m. Above 1000 m up to 4000 m, the output current must be derated by 1 % for each 100 m above 1000 m.
- Environment with pollution degree 2 (as per EN50178 and UL508C).
8
- For operation of the inverter in steady state with output frequencies between 0 and 10 Hz, derate the rated output current by 35 %.
(2) One overload every 10 minutes.
overload curves of the IGBTs for Normal Duty (ND) and Heavy Duty (HD) are presented in
conditions, such as ambient temperature around the inverter and output frequency, the maximum operating time of the inverter with overload may be shorter.
8-2 | CFW-11W G2
Table 8.1: Inverter technical data for rated switching frequencies
Model
]
dc
Nº of UP11
1 min
3 s
For the Coolant
For the Air
1 min
3 s
For the Coolant
For the Air
Chapter 3 INSTALLATION AND CONNECTION on page
Chapter 3 INSTALLATION AND CONNECTION on page
Chapter 3 INSTALLATION AND CONNECTION on page
Table 8.1 on page 8-2
presents only two points of the overload curve (actuation time of 1 min and 3 s). The complete
CFW11W G2
CFW11W G2
CFW11W G2
0780 T 6
1482 T 6
1
2
780
1482
858
1630
1170
2223
2
2
1000/750
2000/1500
3000/2250
897
1704
10,5
21,0
0,2
0,4
640
1216
960
1824
1280
2432
2
2
800/600
1500/1100
2200/1600
736
1398
8,7
17,4
0,2
0,4
3-1. For higher temperatures, limited to 55 º C, the
3-1.
Figure 8.1 on page
CFW11W G2
CFW11W G2
2223 T 6
2964 T 6
3705 T 6
574...1150
3
4
2223
2964
2445
3260
3335
4446
2
2
4000/3000
5000/3750
2556
3409
31,5
42,0
0,6
0,8
1824
2432
2736
3648
3648
4864
2
2
3000/2200
3800/2800
2098
2797
26,1
34,8
0,6
0,8
3-1. For higher temperatures, limited
8-3. Depending on the inverter operating
5
3705
4076
5558
2
4261
52,5
1,0
3040
4560
6080
2
3496
43,5
1,0

Advertisement