5.2.2 Oriented Start-up

In order to simplify the setting of the inverter, there is a parameter group called Oriented Start-Up. Within this group
is parameter P0317, which can be used to access the Oriented Start-Up.
The Oriented Start-up routine shows on the HMI the main parameters in a logical sequence, so that their setting,
according to the operating conditions, prepares the inverter for operation according to the supply voltage and
motor used.
In order to enter an Oriented Start-up routine, follow the sequence presented in
changing P0317 = 1, and then setting the other parameters as they are displayed on the HMI.
The setting of the parameters presented in this operating mode automatically changes the content of other inverter
parameters and/or internal variables.
During the Oriented Start-Up routine the "Config" (Configuration) status will be indicated on the top left part of
the HMI.
Step
Action/Result
1
- Monitoring mode
- Press "Menu" (right soft
key)
2
- Group "00 ALL
PARAMETERS" has been
already selected
3
- Group "01 PARAMETER
GROUPS" is selected
- Group "02 ORIENTED
4
START-UP" is then selected
- Press "Select"
Display Indication
Ready
LOC
0rpm
0
rpm
0.0
A
0.0
Hz
13:48
Menu
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
LOC
0rpm
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Energization and Start-Up
Figure 5.2 on page
Step
Action/Result
11
- If needed, change the
value of P0298 according
to the inverter application.
To do so, press "Select".
This modification will affect
P0156, P0157, P0158, P0401,
P0404 and P0410 (this last
one only if P0202 = 0, 1, or
2 - V/f control). The time and
the activation level of the
overload protection will be
affected as well
12
- If needed, change the
value of P0398 according
to the motor service factor
To do so, press "Select"
This modification will affect
the current value and the
activation time of the motor
overload function
13
- If needed, change the
value of P0400 according
to the motor rated voltage
To do so, press "Select"
This modification adjusts
the output voltage by a
factor x = P0400/P0296
- If needed, change the
14
value of P0401 according
to the motor rated current.
To do so, press "Select".
This modification will affect
P0156, P0157, P0158, and
P0410
5-4, first
Display Indication
Config
LOC
0rpm
Line Rated Voltage
P0296: 500 - 525 V
Application
P0298: Heavy Duty
Reset
13:48
Select
Config
0rpm
LOC
Application
P0298: Heavy Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
Config
LOC
0rpm
Motor Service Factor
P0398:
1.15
Motor Rated Voltage
P0400:
525 V
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Voltage
P0400:
440V
Motor Rated Current
P0401:
30.2 A
Reset
13:48
Select
CFW-11W G2 | 5-3