Crestron CLS-C6/C6M & CLSI-C6/C6M
Operations Guide – DOC. 6347E
Building Management System Integration
Crestron CLS-C6 includes BMS integration capabilities for straightforward inclusion
of building management systems as a component of managing energy demands.
Control System Integration
The CLS-C6 actually features two separate Cresnet
devices and one for connection to a 2-Series control system.
Connecting the CLS-C6 to a control system allows its functions to be controlled
from touch screens, RF wireless remotes, and even computers, supporting extensive
flexibility for remote control and integration with other devices and systems.
Additional functions such as on-the-fly room combining and activating operations
based on a real-time clock are also made possible by connecting the CLS-C6 to a
control system.
Connecting to an Ethernet-networked control system provides a gateway to larger
applications such as integration with facility-wide lighting, HVAC, security, and
remote monitoring via Crestron RoomView
party SNMP software.
RS-232 Interface via C2N-IO
The CLS-C6 can be controlled from a third party controller or a PC program via the
ASCII command set. The Crestron serial convertor module, C2N-IO (sold
separately), is used to route packets between the CLS-C6 and the third party
controller. The serial converter module translates ASCII strings to Cresnet serial
packets and Cresnet serial packets to ASCII strings.

Specifications

Specifications for the CLS-C6 are listed in the following table.
CLS-C6 Specifications
SPECIFICATION
Load Ratings
CLS-C6/C6M
Dimmer channels
Max load per channel
Min load per channel
Max load per unit:
CLSI-C6/C6M
Dimmer Channels
Max load per channel
Min load per channel
Max load per unit:
Load Types
Power Requirements
Default Net ID
(Continued on following page)
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M • 4
iLux Integrated Lighting System
®
control networks, one for local
®
Help Desk software as well as third-
DETAILS
6
800 W/VA (6.7 Amps @ 120 VAC)
15 W/VA (0.125 Amps @ 120 VAC)
1920 W/VA (16 Amps @ 120 VAC)
6
800 W/VA (3.5 Amps @ 230 VAC)
25 W/VA (0.108 Amps @ 230 VAC)
2200 W/VA (10 Amps @ 220 VAC)
2300 W/VA (10 Amps @ 230 VAC)
2400 W/VA (10 Amps @ 240 VAC)
1
LED
, Incandescent, Magnetic Low-voltage,
Neon/Cold Cathode, 2-Wire Dimmable
Fluorescent, & Non-Dim Lighting (also: Electronic
Low-voltage, 3 and 4-Wire Fluorescent, High-
Inrush Switching, & 277V via CLS-EXP Series
2
expansion modules
)
CLS-C6/C6M Line Power, 100 –127 VAC, 50 /
60Hz
CLSI-C6/C6M Line Power, 220 – 240 VAC, 50 /
60Hz
1F