Adding C2N-Io Device To Cls-C6; Echo Control Command; Light Zone Commands - Crestron iLux CLS-C6 Series Operation Manual

Integrated lighting system
Hide thumbs Also See for iLux CLS-C6 Series:
Table of Contents

Advertisement

Crestron CLS-C6/C6M & CLSI-C6/C6M
RS-232 Command Table (Continued)
COMMAND
DESCRIPTION
CATEGORY
Occupancy
Read
occupancy
state
Photocell
Read
Photocell
active state
Version
Read version
number
NOTE: Command and response parameters are separated by blank space characters.
Light Zone Operation
Commands
Operations Guide – DOC. 6347E
COMMAND
[ILUX] OC ?
[ILUX] PH [X|ALL] ACTIVE ?
[ILUX] VER ?

Adding C2N-IO Device to CLS-C6

To add a C2N-IO module to CLS-C6 connect the module to the CLS-C6 Cresnet
slave network port and run the auto-discover from CLS-C6 front panel. CLS-C6 adds
the device to its network list. The CLS-C6 then polls and configures the C2N-IO
serial port.
The C2N-IO serial port baud rate settings are 9600, 8 data bits, 1 stop bit,
XON/XOFF disabled, RTS/CTS disabled.

Echo Control Command

This command is used to enable/disable character echo.
Syntax: [ILUX] Echo [ON|OFF]

Light Zone Commands

Light zone Level Command
The following command is used to set the light zone levels:
Syntax: [ILUX] LZ [X|ALL] LVL [LEVEL] [FADETIME]
X=1 - 6 light zone
ALL = ALL light zones
FADETIME=0 - 594000 in 0.01 second steps (e.g. 100=1 seconds)
LEVEL:
LEVEL IN PERCENT
0
1 to 100
Light zone Level Recall Command
The following command is used to get the light zones level:
Syntax: [ILUX] LZ [X|ALL] LVL?
X = 1 - 6 light zone
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M • 62
iLux Integrated Lighting System
[ILUX] OC [STATE]
[ILUX] PH [X] ACTIVE
[STATE1][...][STATE6]
[ILUX] VER [ID STRING]
DESCRIPTION
Level off
Level On
RESPONSE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents