Crestron iLux CLS-C6 Series Operation Manual page 42

Integrated lighting system
Hide thumbs Also See for iLux CLS-C6 Series:
Table of Contents

Advertisement

Crestron CLS-C6/C6M & CLSI-C6/C6M
Lights Mode
Manual Load Adjustment With
Daylight Harvesting
When a load is under photocell
control, the top bar graph LED for
that load blinks slowly. Manual
adjustment of the load is still
possible using the raise and lower
buttons.
NOTE: Manual adjustment of the
load does not disable the photocell.
The load changes in response to the
photocell, but the level is shifted up
or down according to an internal
calculation that compensates for the
amount of manual adjustment.
Operations Guide – DOC. 6347E
Unit 2 (Cresnet ID 0xC6): Defeat Occ Sensors/lockout front panel controls
Unit 3 (Cresnet ID 0xC7): Recall scenes 14/15
Unit 4 (Cresnet ID 0xC8): Override mode/load shed
For these units, DIP switches 0, 1, 2, and 3 determines whether the inputs are
normally open, normally closed, active high or active low.
In order for the DIN-IO8 to be compatible with any model of BMS, one Cresnet ID
treats the inputs as normally open. That is, a closure activates the function. Another
Cresnet ID treats the inputs as normally closed.
When inputs are treated as normally open, port 8 shall cause a short to ground when
the room is considered occupied.
When inputs are treated as normally closed, port 8 shall cause a short to ground
when room is considered unoccupied.
Lights mode is used to manually adjust any of the six lighting loads.
To enter Lights mode, raise the cover and press the Lights button. The corresponding
LED lights, and the six function buttons can now be used to adjust lighting loads 1
through 6. Any scenes that are currently in the middle of a fade immediately goes to
their target value. The seven white front panel LEDs go out. In this mode, these
LEDs do not reflect the feedback status of the associated scenes. When returning to
Standard mode, the LEDs return to their standard feedback indication.
Pressing the right side of one of the six function buttons raises the corresponding
lighting load at the ramp rate. Pressing the left side of the button lowers the
corresponding load at the ramp rate. When the button is released, the lights stop.
The ramp rate is normally 5 seconds for going from full off to full on. This
can be adjusted using the iLux Designer software. Non-dim lighting loads
go immediately to full on or full off.
The bar graphs indicate current light level.
The two-digit display indicates the current percentage level of the lighting
load being adjusted (oF, 01 to 99, on). This display goes blank 3 seconds
after the last adjustment. While the front panel button is being pressed, the
LED under the corresponding bar graph lights solid to indicate which light
level is being reflected.
The up/down button acts as an All Lights Master when in Lights mode, no
matter what function is programmed for it. The top button performs a
Master Raise (all dimmable lighting loads), and the bottom button performs
a Master Lower (all dimmable lighting loads).
The ON and OFF buttons on the CLS-C6 unit itself operates normally
while in Lights mode as does any Scene Recall, Scene Toggle, and
SceneLts_Off commands from remote panels and Cresnet. However, during
the fade, the two-digit display does not show the fade time on the unit that
is in Lights mode.
All other inputs and commands from any remote devices, motion detector,
and Cresnet control system are processed as usual while in Lights mode. If
they affect the lighting load (or loads) being adjusted, the manual
adjustment of that lighting load is terminated, and the new command takes
precedence. To manually adjust this channel after that, release and re-press
the button. The unit remains in Lights mode.
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M • 38
iLux Integrated Lighting System