Crestron CLS-C6/C6M & CLSI-C6/C6M
Operations Guide – DOC. 6347E
Light Zone Upper Limit Command
The following command is used to get light zone maximum limit. This command is
not supported for slave CLS-C6 controllers:
Syntax: M LZ [X|ALL] MAX ?
X=1...6 light zone
Reply packet
M
LZ
[X|ALL]
LIMITx = 0 - 100 (for light zone 1 through 6)
Light Zone Load Type Command
The following command is used to get load types. This command is not supported
for slave CLS-C6 controllers:
Syntax: M LZ
[X|ALL]
X=1...6 light zone
Reply packet
M
LZ
[X|ALL]
CODEx = refer to table below (type code for light zone through 6):
Light Zone Load Type Codes
SUPPORTED
TYPES CODE
0
1
2
3
4
5
6
7
8
Light Zone Name Query Command
The following command is used to read light zone name:
Syntax: [ILUX] LZ [X|ALL] NAME ?
X=1...6 light zone
Reply packet
[ILUX] LZ [X] NAME [LABEL]
LABEL = Light zone name
[ILUX] LZ ALL NAME [LABEL1], [...], [LABEL6]
LABELx = Light zone names separated by comma
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M • 64
iLux Integrated Lighting System
[MAX] [LIMIT1] [....]
TYPE ?
TYPE [CODE1] [....]
DESCRIPTION
Unused
Non dimmer
Incandescent
Magnetic low voltage
Cold Cathode
Fluorescent 2 wire
Fluorescent 3 wire
Fluorescent 010V
Electronic Low Voltage
[LIMIT6]
[CODE6]