Shade Controllers

A maximum of 16 shade controllers can be added to the local devices network. The
following shade controllers are currently supported (all sold separately):
C2N-SSC-2*
C2N-SDC
C2N-SDC-DC
NOTE: The two channels on these shade controllers are labeled 1 & 2. SIMPL
Windows cannot address the individual Shade Controllers. Only shade groups can be
addressed.
Touch Screens
A maximum of two touch screens can be added to the local devices network. The
following touch screens are currently supported (all sold separately):
TPS-4L
TPS-6L
The iLux auto-assigns the Cresnet ID for the touch screens if they are not already
assigned to one of the designated IDs reserved for the touch screens.
Analog ramps are sent to the touch screens as Ramp Control Blocks, as opposed to
discrete analogs. (In order to properly display analog levels, touch screen firmware
supports Ramp Control Blocks natively.)
Touch screen display lists can be transferred to the touch screen via the programming
jack on the iLux.
Through the use of the join map shown in the tables on the following page, in
conjunction with D-Nav on the touch screen itself, a touch screen connected directly
to an iLux provides the following functionality:
Showing bar graphs indicating the current state of all loads on the master
iLux
Adjusting the level of each load via up/down buttons
Recalling scenes on the master iLux (room combining determines if
additional units are affected)
Programming scenes on the master iLux
Adjusting shades on the master iLux
A button link to the Engraver software is provided in iLux Designer for any touch
screen that is engravable.
Using iLux Designer, only the hard buttons for the selected touch screen can be
programmed. The command list is identical to that for keypads. All "soft buttons" on
the display shall use dedicated join numbers for various functions.
The iLux Designer help file includes a table indicating all the "reserved" joins
supported by the touch screens.
NOTE: These are not the standard reserved joins, but are the join numbers
understood by the CLS-C6 for performing various actions.
* With firmware version 2.5.0 or later
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M • 46
iLux Integrated Lighting System

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents