Command
Parameter block CPU/master OFF
Parameter block CPU/master ON
Delete Logbook - Triggering
operations
Delete Logbook - Events
Cold run ON
Cold run OFF
Delete maintenance timer
3.10.3
Data plausibility check
Description
The motor starter checks all incoming parameters for validity and plausibility.
In the case of incorrect parameters
● During starting (after Power ON), the messages "Group fault" and "Invalid parameter
value" are set.
The motor and the brake output remain switched off.
● During operation, the messages "Invalid parameter value" or "Parameter assignment not
possible in ON state" are set. "Group fault" is not set.
The motor and the brake output are not switched off.
Note
The currently valid parameter values are retained.
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
3.10 Communication over PROFIBUS/PROFINET
Meaning
Motor starter accepts the parameters from the master (PLC)
Motor starter ignores the parameters from the master (PLC)
Delete logbook with recorded fault causes
Delete logbook with recorded warnings and specific actions
Enables activation of the switching contacts without main
power
Switches the "cold run" function off
Deletes the timer of the maintenance function
Functions
69