Event Qualification Timers
Fig. 2.22. Edit the Even Qualification Timer settings from the Edit > Even Qual screen
Use the following steps to configure your Event Qual timer settings:
1. From the Edit menu select from the Event Qual drop down menu.
2. The standard NetGuardian units can have up to 128 Event Quals, which are grouped into sections
of sixteen.
3. Enter the display and point number for the point you wish to qualify in the appropriate ID row.
Note: the ID will correspond to Event Qualification. A list of displays and points can be found in
Appendix B.
5. In the Value field enter the appropriate amount of time (1 - 127).
6. Under the Units column, click on the drop-down menu and select the appropriate unit (min, sec,
hour).
7. Under the Type column click on the drop-down menu and select the appropriate event type (Alm =
alarm, Pri = primary, Sec = secondary).
!
Hot Tip!
To delete the entry, set the Type to None.
8. When you are done making changes, scroll to the bottom of the page and click Submit Data.
CAUTION: Set conditions are qualified, clears are not.
Please note that the alarm qualification event becomes relay momentary time if display and point
reference a control (non-expansion control). Controls are mapped to Display 11, Points 1-8, see
Reference Information Table A1 and A2 for display descriptions, see Reference Information for Display
Mapping Table.