AUMATIC AC 01.1/ACExC 01.1 Profibus DP

5.3.5 Feedback signals (configuration) via analogue output 2: view

5.3.6 Signal range at the analogue output 2: view/edit

34
Configuration of analogue output 2 (of the I/O).
Designation in the wiring diagram: ANOUT2.
This value is set in the factory and can only be changed by the AUMA
service.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
VIEW
I/O1 ANALOG OUT2
TORQUE E6
C:ESC
Default value:
È
Description of the parameter settings:
NOT USED
Analogue output 2 not used.
FEEDBACK E2:
Position feedback (analogue output 2 assigned to actual position signal).
Description see analogue output 1.
TORQUE E6
Analogue torque feedback signal (analogue output 2 assigned to torque sig-
nal). Description see analogue output 1.
Signal range at the analogue output 2 (of the I/O).
This value must correspond to the desired feedback signal.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
EDIT
I/O1 ANALOG OUT1 TYPE
0-20 mA

¿:OK C:ESC
:EDIT
Default value:
È
Description of the parameter settings:
0-20mA
Analogue output 2 generates a 0 – 20 mA signal.
4-20mA
Analogue output 2 generates a 4 – 20 mA signal.
20-0mA
Analogue output 2 generates a 20 – 0 mA signal.
20-4mA
Analogue output 2 generates a 20 – 4 mA signal.
I/O1 ANALOG OUT2 (M410C)
TORQUE E6
I/O1 ANALOG OUT2 TYPE (M411D)
M411D
0-20
m
A
Manual