Signals (Output Signals); Signals Via Profinet; Status Signals Via Output Contacts (Digital Outputs); Assignment Of Outputs - AUMA SQ 05.2 Operation Instructions Manual

Control unit - electromechanical with actuator controls
Hide thumbs Also See for SQ 05.2:
Table of Contents

Advertisement

Signals (output signals)

9.
Signals (output signals)
9.1.

Signals via Profinet

9.2.

Status signals via output contacts (digital outputs)

Conditions
Characteristics
9.2.1.

Assignment of outputs

9.2.2.

Coding the outputs

9.3.

Analogue signals (analogue outputs)

Requirements
50
SQ 05.2
SQ 14.2/SQR 05.2
Feedback signals via Profinet can be configured using the engineering tool of the
DCS/PLC and the GSD file of actuator controls with Profinet (available for download
at www.auma.com).
Refer to Manual Device integration Profinet for information on control commands
and feedback signals via Profinet.
Output contacts are only available if a parallel interface is provided in addition to the
fieldbus interface.
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
The output signals Coding DOUT 1 Coding DOUT 6 can be set either to high active
or low active.
High active = output contact closed = signal active
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2 Coding DOUT 6 = High active
Analogue signals are only available if the following conditions are met:
Actuator controls are equipped with additional control inputs.
The actuator is equipped with a position transmitter (potentiometer, RWG or
EWG).
SQR 14.2 Control unit - electromechanical
AC 01.2 Intrusive Profinet
6) can be assigned to various signals.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents