Output Contacts 1 To 5: Use As Running Indication (Blinker) - AUMA AUMATIC AC 01.1 Manual

Actuator controls
Hide thumbs Also See for AUMATIC AC 01.1:
Table of Contents

Advertisement

Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP

5.2.3 Output contacts 1 to 5: use as running indication (blinker)

Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
OUTPUT CONTACT 1
CLOSING BLINK

:EDIT
È
Description of the parameter settings:
CLOSING BLINK
Signal is active in end position CLOSED.
Signal is blinking for operation in direction CLOSE (depending on the
BLINKER
OPENING BLINK
Signal is active in end position OPEN.
Signal is blinking for operation in direction OPEN (depending on the
BLINKER
Information
The output contacts/LEDs of the local controls (page 19) can also be used
to indicate whether the actuator is operated and if yes, in which direction.
Signal behaviour for BLINKER setting
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EDIT
OFF IN MIDPOSITION

:EDIT
Default value:
È
Description of the parameter settings:
OFF
Signal is active in end position.
Blinker (running indication) is switched off.
LIT IN MIDPOSITION
Signal is active in end position and blinking during operation in direction of
the end position.
The signal remains active in intermediate position.
I/O 1 (M14)
OUTPUT CONTACT 1 (M1412)
OUTPUT CONTACT 2 (M1413)
OUTPUT CONTACT 3 (M1414)
OUTPUT CONTACT 4 (M1415)
OUTPUT CONTACT 5 (M1416)
M1412
¿:OK C:ESC
parameter).
parameter).
LOCAL CONTROLS (M13)
BLINKER (M1311)
M1311
BLINKER
¿:OK C:ESC
OFF IN MIDPOSITION