Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP

7.10.2 Feedback signals on the display

7.10.3 Feedback signals setting via output contacts

7.10.4 Feedback signal setting via LEDs

76
The following indications are displayed in status indications

EMERGENCY STOP
È
Description of the indications:
EMERGENCY STOP/EMCY STOP ACTIVE
The EMERGENCY STOP button has been operated and has put the
AUMATIC into the EMERGENCY STOP status. This status can only be
cancelled by unlocking the EMERGENCY STOP button and issuing a sub-
sequent RESET command.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
I/O 1 (M14)
EDIT
OUTPUT CONTACT 1
EMCY STOP BUTTON

¿:OK C:ESC
:EDIT
È
Description of the parameter settings:
EMCY STOP BUTTON
The selected output contact is activated, after the EMERGENCY STOP but-
ton was operated.
This signal can be cancelled by unlocking the EMERGENCY STOP button.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
LOCAL CONTROLS (M13)
EDIT
LED 2
EMCY STOP BUTTON

¿:OK C:ESC
:EDIT
È
Description of the parameter settings:
EMCY STOP BUTTON
The selected LED is illuminated after the EMERGENCY STOP button was
operated.
This signal can be cancelled by unlocking the EMERGENCY STOP button.

S0
NOT READY IND,
EMCY STOP ACTIVE
OUTPUT CONTACT 1 - 5