AUMA AUMATIC AC 01.1 Manual page 87

Actuator controls
Hide thumbs Also See for AUMATIC AC 01.1:
Table of Contents

Advertisement

Manual
Setting the max. permissible number of starts
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MONITOR TRIGGERS (M18)
EDIT
MAX STARTS/HOUR
1200

¿:OK C:ESC
:EDIT
Default value:
Setting range:
Setting the max. permissible running time
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MONITOR TRIGGERS (M18)
EDIT
MAX DUTY CYCLE
15 min

¿:OK C:ESC
:EDIT
Default value:
È
Description of the parameter settings:
15 MIN
The max. permissible running time (on-time) per hour amounts to 15 min.
24 MIN
The max. permissible running time (on-time) per hour amounts to 24 min.
30 MIN
The max. permissible running time (on-time) per hour amounts to 30 min.
AUMATIC AC 01.1/ACExC 01.1 Profibus DP
MAX STARTS/HOUR (M1810)
M1810
1200
0
to
1800
starts (motor starts)
MAX DUTY CYCLE (M1811)
M1811
15 MIN
Actuator controls
87